Skip to main content
Schneider Electric A9P54316

Schneider Electric A9P54316 Acti9 iC40N MCB, 16 A, 3P, C Cur

MPN A9P54316
Active

Schneider Electric Acti9 iC40N miniature circuit breaker, A9P54316, 16 A, 3P, C curve, 10 kA Icu at 400 V AC, thermal-magnetic, clip-on DIN rail.

$105.79 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9P54316 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V AC 50/60 Hz
Insulation voltage ui440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

A9P54316 additional specifications
ParameterValue
ColorWhite
Depth74 mm
Width54 mm
Height85 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric A9P54316 is an Acti9 iC40N miniature circuit breaker rated 16 A, 3-pole, C-curve, with a breaking capacity of 10 kA Icu at 400 V AC per EN/IEC 60947-2 and 6 kA Icn at 400 V AC per EN/IEC 60898-1. It is a thermal-magnetic trip unit, clip-mounted on DIN rail, and carries a current lifecycle status.

Breaking capacity and dual-standard rating

The 10 kA Icu rating under EN/IEC 60947-2 is the ultimate short-circuit capacity the breaker can interrupt once and remain functional; the 6 kA Icn under EN/IEC 60898-1 is the service capacity for repeated faults in a residential or light commercial distribution board. For a 16 A, 3P MCB in a 400 V AC panel, 10 kA Icu gives solid headroom above typical 6 kA or 10 kA prospective fault levels — it won't be the weak link in a selectivity study.

C-curve trip characteristic

The C curve has a magnetic trip threshold of 5 to 10 times In (80 to 160 A for this 16 A unit) per EN/IEC 60898-1, and 8 x In ±20 % per EN/IEC 60947-2. That's the standard choice for mixed resistive-inductive loads — lighting, small motors, general-purpose socket circuits — where inrush is moderate and nuisance tripping on start-up is unlikely.

Clip-on mounting to DIN rail, 6 module pitches (54 mm wide), tunnel terminals top and bottom accepting 1 to 16 mm² rigid or 1 to 10 mm² flexible. Tightening torque 2 N·m, strip length 14 mm. IP20 finger-safe terminals, IP40 in the modular enclosure — standard for a distribution board. The locking option via padlocking device suits lockout/tagout procedures.

MPN
A9P54316