The A9P54725: 25 A rated current and C curve (magnetic trip at 5–10 x In per EN/IEC 60898-1, or 8 x In ±20% per EN/IEC 60947-2) means this breaker handles moderate inrush loads like small motor starters and lighting banks without nuisance tripping, but still clears a hard short fast. Dual-rated to both EN/IEC 60898-1 (household-type MCB) and EN/IEC 60947-2 (industrial circuit breaker) standards, so it qualifies for either duty. The 60947-2 rating is what matters for industrial control panels where SCCR coordination is required — the 10 kA Icu figure is the one an inspector or panel builder will look for on the nameplate.
Where it goes in a panel
The 3P+N configuration (three protected poles plus a switched neutral on the left) fits European-style distribution boards where the neutral is switched alongside the phases. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible — enough for a 25 A feed with some headroom. IP20 on the body (finger-safe), IP40 inside a modular enclosure.
The Acti9 iC40N series is a standard catalog item from Schneider, widely specified in European and Middle Eastern distribution projects.