Skip to main content
Schneider Electric A9P55606 — 1-Pole MCB (DIN Rail)

A9P55606 Acti9 iC40H MCB, 6 A, 1P+N, C-curve, 10 kA

MPNA9P55606
Active

Schneider Electric Acti9 iC40H miniature circuit-breaker, A9P55606, 6 A, 1P+N, C-curve, 10 kA Icn at 230 V AC, thermal-magnetic, clip-on DIN rail.

$21.87Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9P55606 — Identification
ParameterValue
Product nameActi9 iC40
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC40H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9P55606 — Electrical & Protection
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In conforming to EN/IEC 60898-1
Breaking capacity (Icu / AIR)10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9P55606 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth74 mm
Tightening torque (by circuit)2 N.m top or bottom
A9P55606 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
A9P55606 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9P55606 — Electrical
ParameterValue
[Ui] rated insulation voltage400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV

Product details

The A9P55606 is a Schneider Electric Acti9 iC40H miniature circuit-breaker rated 6 A with a C-curve, 1P+N poles, and a 10 kA breaking capacity at 230 V AC per EN/IEC 60898-1. The 10 kA Icn means this breaker can safely interrupt a fault current up to 10,000 A at 230 V AC without welding contacts or rupturing the case, which covers most residential and light commercial service-entrance fault levels in a 230 V system. The 1P+N configuration switches the phase and provides a switched neutral that opens and closes with the phase pole, giving full isolation on the outgoing circuit.

Clip-on mounting to a 35 mm DIN rail (EN 60715), 18 mm width (2 x 9 mm pitches) — one standard modular slot. Depth of 74 mm and height of 85 mm fit standard distribution board enclosures. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tightening torque is 2 N.m. The white housing with toggle and trip-indicator flag gives clear visual status.

Frequently asked questions

What are the key ratings for the A9P55606?

6 A rated current, C-curve (magnetic trip 5–10 x In), 1P+N poles, 10 kA breaking capacity at 230 V AC per EN/IEC 60898-1, thermal-magnetic trip, limitation class 3, suitable for isolation.

What compliance standards does the A9P55606 meet?

Certified to EN/IEC 60898-1, carries VDE quality label, and meets IP20/IP40 protection per IEC 60529. The manufacturer provides standard RoHS/REACH declarations on request.

MPN