The Schneider Electric A9P55625 is an Acti9 iC40H miniature circuit breaker — a 1P+N thermal-magnetic MCB rated 25 A with a C curve, meaning magnetic tripping occurs between 5 and 10 times the rated current (125–250 A). Breaking capacity is 10 000 A Icn at 230 V AC, 50/60 Hz, certified to EN/IEC 60898-1. That 10 kA rating covers most secondary-distribution fault levels in a standard building installation; if your upstream transformer or service entrance can deliver more, you'll need a higher-rated upstream device or a current-limiting MCB with a higher Icn. The toggle gives local ON/OFF plus a trip-indicator flag; isolation suitability is marked on the device.
The 18 mm width per module means the 1P+N breaker occupies two 9 mm pitches (18 mm total), so plan your enclosure fill accordingly. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; strip length is 14 mm, tightening torque 2 N.m. IP20 on the body (finger-safe), IP40 inside the modular enclosure.