Skip to main content
Schneider Electric A9P55632 — 1-Pole MCB (DIN Rail)

Schneider Electric A9P55632 Acti9 iC40H MCB, 32 A, C-Curve,

MPNA9P55632
Obsolete

Schneider Electric Acti9 iC40H miniature circuit breaker, A9P55632, 32 A, C-curve, 10 kA Icn at 230 V AC, 1P+N, thermal-magnetic, DIN-rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9P55632 — Identification
ParameterValue
Product nameActi9 iC40
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC40H
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9P55632 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In conforming to EN/IEC 60898-1
Breaking capacity (Icu / AIR)10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9P55632 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth74 mm
Tightening torque (by circuit)2 N.m top or bottom
A9P55632 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
A9P55632 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9P55632 — Electrical
ParameterValue
[Ui] rated insulation voltage400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV

Product details

The Schneider Electric A9P55632 is an Acti9 iC40H miniature circuit breaker (MCB) — a 1P+N thermal-magnetic unit rated at 32 A with a C-curve trip characteristic. The 32 A rating suits general-purpose socket circuits, lighting banks, or small appliance feeds in commercial and residential panels. Breaking capacity is 10,000 A Icn at 230 V AC, 50/60 Hz — enough for most domestic and light commercial installations where the prospective fault current stays under that level. The limitation class is 3 per EN/IEC 60898-1, meaning it lets through limited energy during a fault, which helps with downstream coordination.

The MCB clips onto a DIN rail. It occupies 2 modules of 9 mm pitch (18 mm total width), with the neutral on the left. Height is 85 mm, depth 74 mm. IP20 rated on the front, IP40 inside the modular enclosure — suitable for dry indoor panels. Wire stripping length is 14 mm. The tunnel-type terminals are accessible from top or bottom, making it straightforward to busbar or wire in a panel.

Certified to EN/IEC 60898-1, carrying VDE quality label. Suitability for isolation is marked on the device (contact position indicator shows ON/OFF and trip status). Earth-leakage protection requires a separate residual current block — not integrated. Rated for altitudes up to 2000 m and relative humidity up to 95 % at 55 °C. Electrical durability is 10,000 cycles; mechanical durability 20,000 cycles — typical for a residential-grade MCB.

Frequently asked questions

What is the breaking capacity of A9P55632?

10,000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. This is the standard high-capacity rating for the iC40H variant.

MPN
A9P55632