D-curve timing and coordination
The A9P62716: Magnetic trip threshold is 10 to 14 times In per EN/IEC 60898-1, with a tighter spec of 12 x In ±20 % per EN/IEC 60947-2. For a 16 A breaker, that means instantaneous trip between 160 A and 224 A. That window lets you coordinate downstream with a 10 A C-curve MCB on a motor feeder — the D-curve holds through the inrush, the C-curve clears a fault on the branch. Pollution degree 3 (industrial environment, not just office panels).
Clip-on to DIN rail, neutral on the left. IP20 on the terminals, IP40 inside the modular enclosure — fine for a clean panel, not for washdown. Padlocking device compatible for lockout/tagout. Contact position indicator and trip indicator give visual status without opening the cover.