Schneider Electric A9P62716 Acti9 iC40 MCB, 16 A, 3P+N, D Cu

MPNA9P62716
Active

Schneider Electric Acti9 iC40, miniature circuit breaker, A9P62716, 16 A, 3P+N, D curve, 6 kA Icu at 400 V AC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9P62716 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product nameActi9 iC40
Product rangeActi9
Device applicationDistribution
A9P62716 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]16 A
Rated operational voltage [Ue]400 V AC 50/60 Hz
Rated insulation voltage [Ui]440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage [Uimp]4 kV conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description3P + N
Magnetic tripping limit10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2
A9P62716 — Protection & Performance
ParameterValue
Breaking capacity4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]4500 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 4.5 kA 75 % x Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles
Local signallingON/OFF indication Trip indicator
Contact position indicatorYes
A9P62716 — Mechanical
ParameterValue
Connections / terminalsTunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid
Device short nameiC40
Control typeToggle
Mounting modeClip-on
Mounting supportDIN rail
Usable 9 mm pitches6
Width54 mm
Height85 mm
Depth74 mm
ColourWhite
A9P62716 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-40...85 °C
A9P62716 — Approvals
ParameterValue
StandardsEN/IEC 60898-1 EN/IEC 60947-2
A9P62716 — Specifications
ParameterValue
Curve codeD
Number of protected poles3

Product details

D-curve timing and coordination

The A9P62716: Magnetic trip threshold is 10 to 14 times In per EN/IEC 60898-1, with a tighter spec of 12 x In ±20 % per EN/IEC 60947-2. For a 16 A breaker, that means instantaneous trip between 160 A and 224 A. That window lets you coordinate downstream with a 10 A C-curve MCB on a motor feeder — the D-curve holds through the inrush, the C-curve clears a fault on the branch. Pollution degree 3 (industrial environment, not just office panels).

Clip-on to DIN rail, neutral on the left. IP20 on the terminals, IP40 inside the modular enclosure — fine for a clean panel, not for washdown. Padlocking device compatible for lockout/tagout. Contact position indicator and trip indicator give visual status without opening the cover.

Frequently asked questions

Where can I buy the A9P62716 and get a price?

Sourced to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What does the D curve mean on this 16 A MCB?

The D curve trips magnetically between 10 and 14 times rated current (160–224 A for this 16 A unit), designed for high-inrush loads like motors and transformers where a B or C curve would cause nuisance trips.

What is the breaking capacity of the A9P62716?

4500 A Icn per EN/IEC 60898-1 and 6 kA Icu per EN/IEC 60947-2 at 400 V AC, 50/60 Hz.