Breaking capacity and dual standard rating
The A9P62740 carries two breaking-capacity ratings that govern where it fits: 4.5 kA Icn per EN/IEC 60898-1 for residential or light commercial distribution boards, and 6 kA Icu per EN/IEC 60947-2 for industrial panel applications where the prospective fault current is higher.
D curve — what it means on the line
The D curve trips magnetically between 10 and 14 times the rated current (10–14 x In per EN/IEC 60898-1, with a tighter 12 x In ±20% per EN/IEC 60947-2). If you are protecting a 40 A motor circuit or a control transformer, the D curve is the one that stays closed through the start transient.
The 3P+N body takes 6 module pitches (54 mm wide) on a DIN rail. IP20 finger-safe on the front; IP40 inside a modular enclosure.