Skip to main content
Schneider Electric A9P64602 — 1-Pole MCB (DIN Rail)

Schneider Electric A9P64602 Acti9 iC40N MCB, 2 A, D Curve, 1

MPNA9P64602
Obsolete

Schneider Electric Acti9 iC40N miniature circuit breaker, A9P64602, 2 A rated current, D curve, 1P+N, 10 kA breaking capacity at 230 V AC, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9P64602 — Identification
ParameterValue
Product nameActi9 iC40
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC40N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9P64602 — Electrical & Protection
ParameterValue
Rated current (In)2 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2
Breaking capacity (Icu / AIR)10 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9P64602 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth74 mm
Tightening torque (by circuit)2 N.m top or bottom
A9P64602 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
A9P64602 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1 EN/IEC 60947-2
A9P64602 — Electrical
ParameterValue
[Ui] rated insulation voltage400 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9P64602 is an Acti9 iC40N miniature circuit breaker rated at 2 A with a D tripping curve, configured as 1P+N (single pole plus switched neutral). It breaks up to 10 kA Icu at 230 V AC per EN/IEC 60947-2, and 6 kA Icn per EN/IEC 60898-1. The D curve (magnetic trip at 10–14 × In per 60898-1, 12 × In ±20% per 60947-2) is sized for loads with high inrush, such as small motor starters, solenoid valves, or transformer primaries — the magnetic hold avoids nuisance trips on start-up while still clearing a hard short.

Clip-on mount to DIN rail, 2 modules wide (18 mm per pitch, 9 mm pitches = 2). Neutral is on the left. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip 14 mm, tighten to 2 N·m. IP20 on the terminals, IP40 inside a modular enclosure — standard for distribution boards. The thermal-magnetic trip unit gives you a defined thermal curve for overloads and a magnetic instantaneous element for shorts.

Frequently asked questions

Where can I buy the A9P64602 and how do I get a price?

The A9P64602 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the A9P64602's depth?

The depth is 74 mm.

What compliance documentation does Schneider provide for the A9P64602?

The part is certified to EN/IEC 60898-1 and EN/IEC 60947-2, carries CE marking, and the manufacturer provides a declaration of conformity covering RoHS and REACH compliance.

MPN