Rated 40 A with 30 mA sensitivity, Type AC, it protects outgoing circuits against sinusoidal AC earth faults in residential and commercial final distribution boards. Four poles (4P) cover three-phase plus neutral on a 400…415 V AC 50/60 Hz network. The 30 mA trip threshold is the standard for personal protection against indirect contact in TN and TT systems.
Clip-on mounting to DIN rail (EN/IEC 60715) with a plug-in electrical connection to the adjacent iC60 MCB. The 63 mm width (7 x 9 mm pitches) matches the standard 4P MCB footprint. Bottom tunnel terminals accept 1…35 mm² rigid or 1…25 mm² flexible cable; tighten to 3.5 N·m with 14 mm strip length. IP20 rated (IP40 in modular enclosure), so it lives inside the distribution board, not in a wet location.