Skip to main content
Schneider Electric A9Q14340 — Residual Current Breakers (RCCB/RCBO)

A9Q14340 Vigi iC60 3P 40A 300mA AC Type RCD, Acti9

MPNA9Q14340
Active

Schneider Electric Acti9 Vigi iC60 add-on residual current device, 3P, 40 A, 300 mA, Type AC, instantaneous, 230...415 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Q14340 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9Q14340 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9Q14340 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9Q14340 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules7
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque3.5 N.m bottom
Width63 mm
Height91 mm
Depth73.5 mm
A9Q14340 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9Q14340 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The A9Q14340 is a 3-pole add-on residual current device from the Acti9 Vigi iC60 range, rated 40 A with 300 mA earth-leakage sensitivity, Type AC, instantaneous trip. Rated operational voltage is 230...415 V AC at 50/60 Hz, and it meets EN/IEC 61009-1 and EN/IEC 61009-2-1. That 300 mA sensitivity means it protects against earth faults in circuits where a 30 mA device would nuisance-trip — think lighting, general-purpose socket outlets, or distribution subfeeds where the leakage budget is higher.

IP20 rated for the device body; IP40 when enclosed in a modular enclosure.

Earth-leakage protection is voltage-independent — the trip mechanism doesn't rely on the line voltage to detect a fault, so it still operates even if the neutral is lost upstream. The impulse withstand is 250 A at 8/20 µs waveform per IEC 61009-1, which covers most surge events in a standard distribution board. Rated insulation voltage (Ui) is 500 V AC; rated impulse withstand (Uimp) is 6 kV per IEC 60947-2. Storage temperature range is -40...85 °C; operating range is -5...60 °C.

Frequently asked questions

How do I get current pricing and availability for A9Q14340?

Submit an RFQ against this order code. Availability and current pricing are confirmed at quote time through our independent distribution network.

What is A9Q14340's listed depth?

The depth is 73.5 mm. Overall dimensions are 63 mm wide (7 x 9 mm pitches) and 91 mm high.

What is the closest pin-compatible alternative to A9Q14340 in this component family?

Within the Acti9 Vigi iC60 family, the closest sibling is the same 3P, Type AC, instantaneous format but at a different sensitivity or current rating — for example, a 30 mA version for personnel protection instead of the 300 mA equipment-protection version. The mechanical footprint and DIN pitch are identical across the Vigi iC60 add-on range, so swapping sensitivity or current rating doesn't change the panel layout.

MPN
A9Q14340