Skip to main content
Schneider Electric A9R01225 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R01225 Acti9 iID RCCB, 25A 30mA 2P

MPNA9R01225
Active

Schneider Electric Acti9 iID RCCB, A9R01225, 2P, 25 A, 30 mA, Type A, 220-240 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R01225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R01225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9R01225 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9R01225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73.5 mm
A9R01225 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9R01225 — Approvals
ParameterValue
StandardsEN/IEC 61008-1

Product details

The Schneider Electric A9R01225 is an Acti9 iID residual current circuit breaker (RCCB) — a 2-pole, 25 A unit with 30 mA earth-leakage sensitivity, Type A, rated for 220-240 V AC networks.

Rated breaking capacity Idm / Im is 1500 A at 50/60 Hz. Voltage-independent tripping means the RCCB detects leakage and opens even if the phase voltage collapses — no auxiliary supply needed. That's a reliability advantage in fault scenarios where the neutral might lift.

Terminals accept 1-35 mm² rigid or 1-25 mm² flexible conductors; strip length 14 mm, torque to 3.5 N·m. Neutral on the left, toggle control. IP20 finger-safe (IP40 inside the modular enclosure). Pollution degree 3 — suitable for ordinary indoor panel environments, not sealed for washdown.

Frequently asked questions

What standards does A9R01225 comply with?

It complies with EN/IEC 61008-1, the standard for residual current operated circuit-breakers without integral overcurrent protection for household and similar uses.

MPN
A9R01225