The Schneider Electric A9R01425 is a 4-pole residual current circuit breaker (RCCB) from the Acti9 iID family, rated at 25 A with 30 mA earth-leakage sensitivity. The 30 mA threshold is the standard for personnel protection (shock risk) per most national wiring codes.
Fit and installation
Terminals accept up to 35 mm² rigid or 25 mm² flexible; strip length 14 mm, torque to 3.5 N.m. IP20 finger-safe with the modular enclosure (IP40 inside the panel).
Rated insulation voltage 500 V AC, impulse withstand 6 kV. Breaking capacity Idm = 1500 A, Im = 1500 A.
Storage temperature -40 to 85 °C, operating -25 to 60 °C — fine for most indoor and sheltered outdoor enclosures.