The Schneider Electric A9R05463 is a 4-pole Acti9 iID residual current circuit breaker (RCCB) rated at 63 A with 300 mA earth-leakage sensitivity, Type A, selective time delay.
The selective (time-delayed) characteristic coordinates with downstream 30 mA RCDs: the A9R05463 holds through a transient fault, letting the closer device trip first, so only the faulted branch drops out instead of the whole distribution board. The voltage-independent residual current tripping technology means the RCCB detects leakage and opens even if the phase voltage collapses — a safety advantage over electronic RCDs that need an auxiliary supply to trip.
Clip-on mounting to DIN rail, 8 modules wide (72 mm). Terminals accept 1...35 mm² rigid or 1...25 mm² flexible conductors; strip 14 mm and torque to 3.5 N·m. IP20 finger-safe when installed in an IP40 modular enclosure — standard for distribution boards.