Schneider Electric A9R31492 — Residual Current Breakers (RCCB/RCBO)

Schneider A9R31492 Acti9 RCCB-ID, 4P 125A 30mA Type A-SI

MPNA9R31492
Active

Schneider Electric Acti9 RCCB-ID, 4P, 125 A, 30 mA, Type A-SI, 400 V AC, 50 Hz, grey.

$2,019.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R31492 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationRed/green indicator Trip indicator
A9R31492 — Electrical Ratings
ParameterValue
Rated current (In)125 A
Rated operational voltage (Ue)400 V AC 50 Hz conforming to IEC/EN 61008-1 400 V AC 50 Hz conforming to IEC/EN 61008-2-1
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz conforming to IEC/EN 61008-1 400 V AC 50 Hz conforming to IEC/EN 61008-2-1
Rated impulse withstand voltage (Uimp)4 kV conforming to IEC/EN 61008-1 4 kV conforming to IEC/EN 61008-2-1
Device location in systemOutgoer
Electrical durability2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9R31492 — Identification
ParameterValue
Product nameActi9 RCCB-ID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameRCCB-ID
A9R31492 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminals2 cable(s) 1.5...16 mm² flexible Tunnel type terminals2 cable(s) 1.5...16 mm² rigid Tunnel type terminals1 cable(s) 1.5...50 mm² rigid Tunnel type terminals1 cable(s) 1.5...35 mm² flexible Tunnel type terminals1 cable(s) 1.5...35 mm² flexible with ferrule Tunnel type terminals2 cable(s) 1.5...16 mm² flexible with ferrule
Wire stripping length11 mm
Terminal tightening torque3 N.m
Width72 mm
Height86 mm
Depth76 mm
A9R31492 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC/EN 60529 IP40 (modular enclosure) conforming to IEC/EN 60529
Pollution degree3
A9R31492 — Approvals
ParameterValue
StandardsIEC/EN 61008-1 IEC/EN 61008-2-1

Product details

The Schneider Electric A9R31492 is a 4-pole Acti9 RCCB-ID residual current circuit breaker rated at 125 A with a 30 mA earth-leakage sensitivity, Type A-SI (Super Immunised). The 30 mA sensitivity provides personal protection against direct contact, while the Type A-SI classification means it handles pulsed DC fault currents and is super-immunised against nuisance tripping from high-frequency harmonics or transient surges — critical for circuits with variable-speed drives, UPS systems, or LED lighting where standard Type A RCCBs can false-trip. With an impulse withstand of 3 kA (8/20 µs waveform) per IEC/EN 61008-1 and IEC/EN 61008-2-1, this RCCB tolerates surge events common in industrial mains without unnecessary disconnection.

The 4-pole device occupies 8 x 9 mm pitches (72 mm width), with an 18 mm phase-to-phase connection pitch. Height is 86 mm, depth 76 mm. Tunnel-type terminals accept up to 50 mm² rigid or 35 mm² flexible cable; tightening torque is 3 N·m. IP20 rated for the device body, IP40 for the modular enclosure per IEC/EN 60529. Suitable for installation in enclosed distribution panels where incidental contact protection is sufficient.

Ambient storage range is -40 to 85 °C.

Frequently asked questions

What is the closest alternative to A9R31492 in the Acti9 family?

Within the Acti9 RCCB-ID range, the primary differentiator is the current rating and pole count. The A9R31492 is a 4-pole 125 A Type A-SI unit. For lower current requirements, the same family offers 2-pole and 4-pole variants at 25 A, 40 A, 63 A, and 100 A. All share the same 30 mA sensitivity and Type A-SI characteristic, so the choice is driven by the load current and the number of phases needing protection.

What compliance documentation does Schneider provide for A9R31492?

The A9R31492 carries a VDE quality label and is certified to IEC/EN 61008-1 and IEC/EN 61008-2-1. Standard compliance documentation (declaration of conformity, CE marking) is available from Schneider Electric for this product range.

Where can I buy A9R31492 and get current pricing?

The A9R31492 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for your required quantity.

MPN