Schneider Electric A9R51440 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R51440 Acti9 iID RCCB, 40 A, 30 mA, 4P

MPNA9R51440
Active

Schneider Electric Acti9 iID, A9R51440, 4P RCCB, 40 A, 30 mA, Type A, 400 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R51440 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R51440 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)400 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9R51440 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9R51440 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsSingle terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height91 mm
Depth73.5 mm
A9R51440 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9R51440 — Approvals
ParameterValue
StandardsEN/IEC 61008-1

Product details

The Schneider Electric A9R51440 is an Acti9 iID residual current circuit breaker (RCCB), 4-pole, rated 40 A with 30 mA earth-leakage sensitivity. Rated operational voltage is 400 V AC at 50/60 Hz, with a breaking capacity of Idm 1500 A / Im 1500 A. That's enough for outgoing feeder protection in a distribution board where you need ground-fault isolation on a three-phase circuit.

Clip-on mount to DIN rail, 8 x 9 mm pitch modules wide (72 mm). Depth is 73.5 mm, height 91 mm — standard modular footprint for a 4P RCCB. Neutral on the left, toggle control. Terminals accept up to 35 mm² rigid or 25 mm² flexible, with a stripping length of 14 mm and torque of 3.5 N.m. IP20 on the body, IP40 inside a modular enclosure. That's a panel-friendly profile for a 40 A device.

Built to EN/IEC 61008-1. Pollution degree 3, rated insulation voltage 500 V AC. Electrical durability 15,000 cycles (AC-1), mechanical 20,000 cycles. Voltage-independent residual current tripping — no auxiliary supply needed. Instantaneous tripping, no intentional delay.

Frequently asked questions

What is the rated current and sensitivity of A9R51440?

Rated current is 40 A with 30 mA earth-leakage sensitivity, Type A, 4-pole.

What standards does A9R51440 comply with?

It complies with EN/IEC 61008-1.

Where can I buy A9R51440?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN