Four poles (4P), Type AC detection, designed for 380...415 V AC 50/60 Hz networks.
300 mA sensitivity is for fire protection, not personnel shock protection. The 6 kV impulse withstand voltage (Uimp) matches the overvoltage category for fixed installations at the outgoer position. Neutral on the left. Terminals accept up to 35 mm² rigid or 25 mm² flexible; wire strip length 14 mm, torque to 3.5 N.m. IP20 finger-safe, IP40 inside a modular enclosure.
Pollution degree 3. Lifecycle stage is current production.