Skip to main content
Schneider Electric A9S70640 — 1-Pole MCB (DIN Rail)

Schneider A9S70640 Acti9 iSW-NA Switch-Disconnector, 1P+N, 4

MPNA9S70640
Active

Schneider Electric Acti9 iSW-NA switch-disconnector, 1P+N, 40 A, 230/240 V AC, IEC 60947-3, AC-22A, IP20, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9S70640 — Identification
ParameterValue
Product nameActi9 iSW-NA
Product / component typeSwitch disconnector
Product rangeActi9
Device short nameiSW-NA
Poles description1P + N
Device applicationIsolation Control
A9S70640 — Electrical & Protection
ParameterValue
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Control / actuation typeToggle Remote tripping
Mechanical durability (cycles)20000 cycles
A9S70640 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (top or bottom) 1 cable(s) 1...25 mm² flexible with cable end Tunnel type terminals (top or bottom) 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminals (top or bottom) 1 cable(s) 1...35 mm² rigid without cable end
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height85 mm
Depth74 mm
Tightening torque (by circuit)3.5 N.m
A9S70640 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9S70640 — Approvals
ParameterValue
Conformity standardsIEC 60947-3 EN 60947-3
A9S70640 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-3
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-3

Product details

The Schneider A9S70640 is an Acti9 iSW-NA switch-disconnector, 1P+N, rated 40 A at 230/240 V AC. It's rated IP20, so it's for inside an enclosure, not out in the weather. Rated impulse withstand voltage is 6 kV, and it can handle a short-time withstand current of 800 A for 1 second. Short-circuit making capacity is 5 kA as a standalone switch-disconnector. That's the fault-handling capability — enough for most distribution panels downstream of a bigger breaker.

But the AC-22A category is the real spec that matters — it tells you the load type it's tested for: mixed resistive and inductive, up to 40 A. That covers most panel loads: contactors, small motor starters, lighting banks, heaters. Don't use it for pure motor switching above its rating; that's AC-23 duty. That's a solid connection for the current rating — no undersized lugs here. Temperature range is -35 to 70 °C operating, -40 to 85 °C storage. Tropicalisation class 2 means it's treated for humid environments up to 95% RH at 55 °C.

Frequently asked questions

What is A9S70640's listed depth?

The A9S70640 has a depth of 74 mm. That's the dimension from the DIN rail mounting surface to the front of the device.

What compliance documentation does this brand provide for A9S70640?

The A9S70640 is certified to IEC 60947-3 and EN 60947-3. It carries a pollution degree 3 rating and an IP20 protection degree. RoHS and REACH compliance is standard for the Acti9 range, though specific declarations should be confirmed at quote time.

MPN