Skip to main content
Schneider Electric A9TAB2625 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9TAB2625 Acti9 iC40 ARC, 25 A, 1P+N, Arc

MPNA9TAB2625
Active

Schneider Electric Acti9 Active ARC iC40, A9TAB2625, 25 A, 1P+N, 230 V AC, arc fault detection add-on block, EN/IEC 62606, IP20, DIN rail clip-on, 2-module width (36 mm).

$353.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TAB2625 — Residual Current Protection
ParameterValue
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TAB2625 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC 50 Hz conforming to IEC 62606
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV conforming to IEC 62606
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability10000 cycles 230 V AC conforming to IEC 62606
Mechanical durability (operating cycles)20000 cycles
A9TAB2625 — Identification
ParameterValue
Product nameActi9 Active ARC iC40
Product / component typeActive arc fault detection add-on block
Device short nameiC40 ARC
A9TAB2625 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules2
Terminal connectionsTunnel type terminal1...10 mm² flexible Tunnel type terminal1...16 mm² rigid
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TAB2625 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20
Pollution degree2 conforming to IEC 62606
Relative humidity95 % at 55 °C
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TAB2625 — Approvals
ParameterValue
StandardsEN/IEC 62606

Product details

The A9TAB2625: The 25 A rated current (In) is the continuous load the block is designed to pass; match it to the upstream MCB's rating for coordinated arc-fault protection. The 275 V ±5 V overvoltage threshold trips the internal mechanism when line voltage exceeds that window — useful for catching neutral-to-earth faults or sustained swells that can ignite an arc. Accuracy on voltage and current is ±2 %, power ±5 %, so the event-logging data is repeatable enough for post-incident analysis. The IP20 housing keeps fingers out but is not sealed; mount inside a closed panel.

Clip-on mounting on DIN rail, neutral on the left. The tunnel-type terminals accept 1–10 mm² flexible or 1–16 mm² rigid; strip length 14 mm, tighten to 2 N·m. The block connects to the MCB by screws — no separate busbar needed. Local signalling includes ON/OFF status, a fault-trip LED, and an arc-fault diagnostic LED for troubleshooting without a meter. Electrical durability is 10,000 cycles at 230 V AC per IEC 62606; mechanical durability is 20,000 cycles. The block records date/time and maintenance indicators, and is compatible with EcoStruxure Panel Server concentrators for remote monitoring.

MPN
A9TAB2625