Skip to main content
Schneider Electric A9TDF3625 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9TDF3625 Acti9 iCV40 ARC RCBO, 25 A C-cu

MPNA9TDF3625
Active

Schneider Electric Acti9 iCV40 ARC, RCBO, 1P+N, 25 A, C-curve, 6 kA Icn / 10 kA Icu at 230 V AC, clip-on DIN rail, IP20.

$329.99Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDF3625 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDF3625 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDF3625 — Identification
ParameterValue
Product nameActi9 iCV40 ARC
Product / component typeArc fault detection RCBO
Product range / familyActi9
Device short nameiCV40N ARC
A9TDF3625 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDF3625 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDF3625 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The Schneider Electric A9TDF3625 is an Acti9 iCV40 ARC residual current circuit breaker with integral overcurrent protection (RCBO) in a 1P+N format, rated 25 A with a C-curve trip characteristic. It combines earth-leakage detection and thermal-magnetic overcurrent protection in one DIN-rail module, saving a panel row compared to separate RCCB + MCB. Breaking capacity is 6 kA Icn (service) and 10 kA Icu (ultimate) at 230 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2 respectively. Magnetic tripping threshold is 5 to 10 times In, typical for C-curve.

IP20 front. Neutral on the left — verify orientation when replacing an existing RCBO with neutral on the right.

Current production. Quality marks from IMQ, AENOR, and OVE. Tropicalisation severity B per IEC 60068-2-30.

Frequently asked questions

What is the closest alternative to A9TDF3625 in the same family?

Within the Acti9 iCV40 range, the main variant difference is the rated current (In) and curve code. This is the 25 A C-curve version; an iCV40 with a different In or B/D curve would be the natural alternative if the load profile differs.

What compliance documentation does Schneider provide for A9TDF3625?

The part carries EN/IEC 62606, EN/IEC 61009-1, EN/IEC 60947-2, and EN/IEC 61009-2-1 certifications, plus quality marks IMQ, AENOR, and OVE. It also meets tropicalisation severity B per IEC 60068-2-30.