Cable entry is from top and bottom, with a wire stripping length of 14 mm and a tightening torque of 2 N.m. Neutral is on the left. Breaking capacity is 6000 A Icn at 230 V AC per EN/IEC 61009-2-1, and 10 kA Icu at 230 V AC per EN/IEC 60947-2. It measures voltage, active power, current, and power factor with stated accuracy of ±2% for voltage and current, ±5% for power. Local signalling includes ON, OFF, a fault-trip LED, and an arc-fault diagnostic LED — useful for a panel builder or field tech isolating a tripped circuit without a meter.
Standards, approvals, and environmental rating
Carries quality labels IMQ, AENOR, and OVE — accepted across European and some Latin American jurisdictions. Pollution degree 2 per EN/IEC 62606, overvoltage category III, tropicalisation severity B per IEC 60068-2-30 for 28 days (95% RH at 55 °C). Thermal-magnetic trip unit technology, limitation class 3. Total power losses 3.408 W (2.65 W per pole).