Skip to main content
Schneider Electric A9TYA4240

Schneider Electric A9TYA4240 Acti9 VigiARC iC60, 40 A, 30 mA

MPN A9TYA4240
Active

Schneider Electric Acti9 VigiARC iC60, arc-fault detection with residual current protection add-on block, 2P, 40 A, 30 mA, 230 V AC, DIN rail clip-on.

$329.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9TYA4240 specifications
ParameterValue
Voltage230 V AC
Insulation voltage ui400 V AC
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree2
ColorWhite (RAL 9003)
Depth73 mm
Width54 mm
Height91 mm
Electrical life cycles10000 cycles > 25 A 20000 cycles <= 25 A
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

The Schneider Electric A9TYA4240 is an Acti9 VigiARC iC60 arc-fault detection device (AFDD) combined with a 30 mA residual current device (RCD) in a single add-on block, 2-pole, rated 40 A at 230 V AC. The 40 A [In] and 30 mA sensitivity cover typical final circuits supplying socket outlets or fixed equipment in residential and light commercial installations. The Type A-SI (Super Immunised) earth-leakage class means it resists nuisance tripping from high-frequency leakage or pulsed DC waveforms common on modern electronics. Rated impulse withstand voltage is 4 kV (Uimp), insulation voltage 400 V AC (Ui), and pollution degree 2 — suitable for standard indoor panel environments. Operating temperature range is -25 to 60 °C, storage -40 to 85 °C, with tropicalisation severity B per IEC 60068-2-30 for 28 days.

Neutral is on the left. Local signalling includes ON/OFF status, a fault-trip LED, and an arc-fault diagnostic indicator. Electrical durability: 10,000 cycles above 25 A, 20,000 cycles at or below 25 A; mechanical durability 20,000 cycles. The device records date/time of events and maintenance indicators.

MPN
A9TYA4240