Specifications

A9TYBE225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TYBE225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability10000 cycles > 25 A 20000 cycles <= 25 A
Mechanical durability (operating cycles)20000 cycles
A9TYBE225 — Identification
ParameterValue
Product nameActi9 Active VigiARC iC60
Product / component typeActive arc fault detection with residual current protection add-on block
Device short nameVigiARC iC60
A9TYBE225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules2
Terminal connectionsTunnel type terminals1...10 mm² flexible Tunnel type terminals1...16 mm² rigid
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width54 mm
Height91 mm
Depth73 mm
A9TYBE225 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TYBE225 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1

Product details

It monitors for series and parallel arcing faults per EN/IEC 62606 while providing 30 mA earth-leakage protection per EN/IEC 61009-1 and -2-1. The unit integrates overvoltage, earth-leakage, and overload event management with local signalling via ON/OFF/fault-trip LED and an arc-fault diagnostic indicator.

Rated at 25 A (In) on a 230 V AC, 50 Hz network, this device is sized for a final subcircuit supplying a single branch — lighting, socket outlets, or fixed equipment within that current envelope. The 30 mA earth-leakage sensitivity (Type A-SI, Super Immunised) makes it suitable for circuits where nuisance tripping from high-frequency leakage or pulsed DC fault currents is a concern; the SI designation indicates a higher immunity to transient surges than standard Type A. The overvoltage trip threshold is set at 275 V ±5 V, which protects downstream equipment if a neutral loss or supply swell pushes the phase voltage above that level. Measurement accuracy is ±2 % for voltage and current, ±5 % for active power — adequate for energy monitoring and fault logging via the EcoStruxure Panel Server concentrators (Entry, Advanced, or Universal). Electrical durability is rated at 20,000 cycles at or below 25 A, and 10,000 cycles above 25 A; mechanical durability is 20,000 cycles. These figures govern the expected service life under normal switching duty — not fault interruption, which is covered by the short-circuit breaking capacity of the upstream MCB.

Neutral is on the left. Tunnel-type terminals accept 1–10 mm² flexible or 1–16 mm² rigid conductors; tighten to 2 N·m with a 14 mm strip length. IP20 rated — suitable for dry indoor enclosures only.

Compliant with EN/IEC 62606 (arc fault detection devices), EN/IEC 61009-1 (RCBOs general rules), and EN/IEC 61009-2-1 (RCBOs functional independence). Carries the IMQ quality mark. Tropicalisation severity B per IEC 60068-2-30 for 28 days. Pollution degree 2. Operating altitude limited to 2000 m.

Frequently asked questions

How do I get current pricing and availability for A9TYBE225?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

What is A9TYBE225's listed depth?

The depth is 73 mm.

What is A9TYBE225's listed width?

The width is 54 mm, occupying 2 modules of 9 mm pitch on a DIN rail.

What compliance documentation does Schneider provide for A9TYBE225?

The device is certified to EN/IEC 62606, EN/IEC 61009-1, and EN/IEC 61009-2-1, and carries the IMQ quality mark. Tropicalisation per IEC 60068-2-30 severity B is also documented.

MPN
A9TYBE225