Skip to main content
Schneider Electric A9V14325 — Residual Current Breakers (RCCB/RCBO)

A9V14325 Acti9 Vigi iC60 3P 25A 300mA RCD, Obsolete

MPNA9V14325
Obsolete

Schneider Electric Acti9 Vigi iC60, add-on residual current device, 3P, 25 A, 300 mA, Type AC, instantaneous, voltage independent, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9V14325 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9V14325 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)400 V AC 50/60 Hz conforming to EN 61009-1 400/415 V AC 50/60 Hz conforming to IEC 61009-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9V14325 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9V14325 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules6
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque2 N.m bottom
Width54 mm
Height91 mm
Depth73.5 mm
A9V14325 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9V14325 — Approvals
ParameterValue
StandardsEN 61009-1 IEC 61009-1

Product details

The Schneider Electric A9V14325 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a 3-pole, 25 A, 300 mA Type AC block that clips onto the outgoer side of a compatible iC60 MCB. It's voltage-independent, so it trips on residual current even if the line voltage drops, and it's rated for 400 V AC networks at 50/60 Hz. The 300 mA sensitivity makes it suitable for general protection against earth faults where a higher threshold is acceptable, such as on distribution sub-mains or circuits with high leakage from connected equipment.

Mounts via clip-on to DIN rail, occupying 6 x 9 mm pitches (54 mm width). The bottom tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable, with a stripping length of 14 mm and a tightening torque of 2 N.m. Electrical connection to the upstream MCB is made by screws.

Pollution degree 3 per IEC 60947-2 covers industrial environments with conductive or dry non-conductive pollution. The device complies with EN 61009-1 and IEC 61009-1.

Frequently asked questions

What compliance documentation does this brand provide for A9V14325?

The A9V14325 is certified to EN 61009-1 and IEC 61009-1. It carries an IP20/IP40 rating per IEC 60529 and pollution degree 3 per IEC 60947-2. Specific RoHS/REACH/UL documentation should be requested at quote time.

MPN
A9V14325