Skip to main content
Schneider Electric A9V19263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9V19263 Vigi iC60 RCD, 2P 63A AC type se

MPNA9V19263
Obsolete

Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 63 A, AC type, selective, 1000 mA, 230…415 VAC, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9V19263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)1000 mA
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9V19263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9V19263 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9V19263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules4
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque3.5 N.m bottom
Width72 mm
Height91 mm
Depth73.5 mm
A9V19263 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9V19263 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider Electric A9V19263 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a voltage-independent, 2-pole unit rated 63 A with a 1000 mA AC-type earth-leakage sensitivity, selective time delay, and 230…415 VAC operational range.

The A9V19263 is listed as Obsolete by Schneider Electric. If you are maintaining a panel design that specifies this part, verify whether the wider Acti9 Vigi iC60 range has a current-production variant with the same 2P, 63 A, 1000 mA, AC-type, selective parameters — the physical footprint and connection scheme are consistent across the family, but the order code change and any certification recertification need checking against your assembly documentation.

Wiring and panel integration

Mounts by clip-on onto a DIN rail, occupying 4 x 9 mm pitches (72 mm width). The bottom side is also compatible with comb busbars and distribution blocks, so it can be fed from a common busbar run alongside the MCB. IP20 on the device body, IP40 inside a modular enclosure. Pollution degree 3 per IEC 60947-2 — suitable for standard industrial panel environments, not sealed outdoor locations.

Rated insulation voltage 500 V AC; impulse withstand 6 kV per IEC 60947-2. Impulse withstand on the residual current path: 8/20 µs, 3000 A per IEC 61009-1. Ambient operation -5…60 °C, storage -40…85 °C.

Frequently asked questions

What is the difference between AC type and A type RCD?

AC type (this unit) detects sinusoidal AC earth-leakage current only. It does not detect pulsed DC or smooth DC fault currents. If your load includes rectifiers, VFDs, or switching power supplies that can generate DC leakage, an A type or B type RCD would be required. The A9V19263 is AC type only.

MPN
A9V19263