Skip to main content
Schneider Electric A9V26225 — Residual Current Breakers (RCCB/RCBO)

Schneider A9V26225 Acti9 Vigi iC60, 2P 25A 500mA, Obsolete

MPNA9V26225
Obsolete

Schneider Electric Acti9 Vigi iC60 add-on residual current device, 2P, 25 A rated current, 500 mA sensitivity, Type A earth leakage protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9V26225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)500 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9V26225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9V26225 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9V26225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules3
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque2 N.m bottom
Width63 mm
Height91 mm
Depth73.5 mm
A9V26225 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9V26225 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider A9V26225 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a voltage-independent, Type A earth-leakage module that clips onto the outgoing side of an Acti9 iC60 MCB. Rated 25 A continuous with 500 mA sensitivity, it protects 2-pole AC circuits at 230…415 V, 50/60 Hz. The 73.5 mm depth and 63 mm width (3 x 9 mm pitches) fit standard DIN-rail enclosures; IP20 body, IP40 in a modular enclosure. This is an add-on RCD, not a standalone device — it mechanically and electrically mates with an Acti9 iC60 MCB via screws, adding earth-leakage protection to the existing overcurrent circuit. The trip indicator on the front gives local status; no auxiliary contacts are built in.

Clip-on mounting to DIN rail, 3 pitches wide (63 mm). Tightening torque 2 N·m; strip length 14 mm. The comb-busbar compatibility is marked 'YES' for the bottom side, so it can share a common neutral/phase bus with adjacent iC60 units.

Key Ratings

Rated insulation voltage 500 V AC; impulse withstand 6 kV. Pollution degree 3 per IEC 60947-2. The 8/20 µs impulse current withstand is 250 A per IEC 61009-1. Ambient temperature range -25…60 °C operating, -40…85 °C storage.

Frequently asked questions

Where can I buy A9V26225?

We source the A9V26225 to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What are the key ratings of A9V26225?

2-pole, 25 A rated current, 500 mA earth-leakage sensitivity, Type A, voltage-independent tripping, 230…415 V AC, 50/60 Hz, DIN-rail mount.

What standards does A9V26225 comply with?

EN/IEC 61009-1 and EN/IEC 61009-2-1 for RCDs; IEC 60947-2 for insulation and impulse withstand.

MPN
A9V26225