Schneider Electric A9W10225 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9W10225 Vigi iC60 RCBO, 25A 10mA AC Type

MPNA9W10225
Obsolete

Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 25 A, 10 mA, AC type, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9W10225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9W10225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230...240 V AC 50/60 Hz conforming to EN 61009-1 230...240 V AC 50/60 Hz conforming to IEC 61009-1
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9W10225 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9W10225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules3
Terminal connectionsTunnel type terminals downside 1...25 mm² rigid Tunnel type terminals downside 1...16 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width63 mm
Height91 mm
Depth74 mm
A9W10225 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9W10225 — Approvals
ParameterValue
StandardsEN 61009-1 IEC 61009-1

Product details

It is a 2-pole unit rated 25 A with a 10 mA AC-type sensitivity, designed for 230–240 V AC 50/60 Hz networks. The clip-on mounting snaps directly onto a DIN rail, occupying 3 module pitches (63 mm wide). The 10 mA sensitivity is the lowest standard threshold for AC-type earth leakage. The instantaneous trip time clears the fault as soon as residual current exceeds 10 mA.

The device is certified to EN 61009-1 and IEC 61009-1. IP20 on the body and IP40 on the modular enclosure.

Frequently asked questions

What is the closest alternative to A9W10225 in the Acti9 family?

No official replacement is listed in the lifecycle record. Within the Acti9 Vigi iC60 range, a functionally similar add-on RCD with the same 2P, 25 A, 10 mA, AC-type ratings would be the closest parametric match, but form-fit-function equivalence must be verified against the specific MCB it mates with. The manufacturer does not document a direct cross-reference.

MPN