Skip to main content
Schneider Electric A9W22263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9W22263 Vigi iC60 RCD, 2P 63A 100mA Type

MPNA9W22263
Obsolete

Schneider Electric Acti9 Vigi iC60, add-on residual current device, 2P, 63 A, 100 mA, Type A, voltage independent, instantaneous, DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9W22263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9W22263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230/415 V AC 50/60 Hz conforming to EN 61009-1
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9W22263 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9W22263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules4
Terminal connectionsTunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible
Wire stripping length14 mm
Terminal tightening torque3.5 N.m
Width72 mm
Height91 mm
Depth74 mm
A9W22263 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9W22263 — Approvals
ParameterValue
StandardsEN 61009-1 IEC 61009-1

Product details

Rated 63 A with 100 mA sensitivity, Type A, 2-pole, it provides instantaneous earth leakage tripping for AC networks at 230/415 V, 50/60 Hz.

The 63 A rated current (In) and 100 mA earth leakage sensitivity define the load and protection threshold. Voltage-independent tripping means the RCD operates without needing a separate power supply; it uses the fault current itself to trigger the mechanism, which makes it inherently fail-safe against loss of control voltage. Rated operational voltage of 230/415 V AC matches standard European single-phase and three-phase distribution. With an insulation voltage (Ui) of 500 V and impulse withstand (Uimp) of 6 kV, the device is coordinated for installation in panels with upstream surge protection. The 4-module width (72 mm, 4 x 9 mm pitches) occupies four DIN spaces — account for that when laying out the panel. IP20 body protection; IP40 inside a modular enclosure.

Designed and certified to EN 61009-1 and IEC 61009-1, the standard for RCDs with integral overcurrent protection (though this is an add-on block, the MCB partner carries the overcurrent function). The 8/20 µs impulse withstand of 250 A per IEC 61009-1 confirms immunity to surge currents from lightning or switching transients.

Frequently asked questions

Where can I buy the A9W22263 and get a price?

We source the A9W22263 through independent distribution channels. Submit an RFQ against this order code; availability and current pricing are confirmed at quote time.

What is the A9W22263's earth leakage sensitivity and type?

100 mA sensitivity, Type A (detects sinusoidal AC and pulsating DC residual currents). Instantaneous trip, voltage-independent operation.

What are the A9W22263's mounting and terminal specs?

Clip-on DIN rail mount, 4-module width (72 mm). Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; tightening torque 3.5 N·m; strip length 14 mm.

MPN
A9W22263