Skip to main content
Schneider Electric A9W24363 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9W24363 Acti9 Vigi iC60, 63A 300mA Type

MPNA9W24363
Active

Schneider Electric Acti9 Vigi iC60 add-on residual current device, 3P, 63 A, 300 mA Type A instantaneous, 400 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9W24363 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationTrip indicator
A9W24363 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)400 V AC 50/60 Hz conforming to EN 61009-1 230/415 V AC 50/60 Hz conforming to IEC 61009-1
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer
A9W24363 — Identification
ParameterValue
Product nameActi9 Vigi iC60
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi iC60
A9W24363 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules7
Terminal connectionsTunnel type terminals downside 1...35 mm² rigid Tunnel type terminals downside 1...25 mm² flexible
Wire stripping length14 mm
Terminal tightening torque3.5 N.m
Width117 mm
Height91 mm
Depth74 mm
A9W24363 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
A9W24363 — Approvals
ParameterValue
StandardsEN 61009-1 IEC 61009-1

Product details

The Schneider Electric A9W24363 is an Acti9 Vigi iC60 add-on residual current device (RCD) rated 63 A with 300 mA Type A earth leakage protection, instantaneous trip, and voltage-independent tripping technology.

63 A rated current (In) matches the downstream iC60 MCB rating — pair them for coordinated overcurrent and earth leakage protection on a 63 A circuit. 300 mA sensitivity is typical for submain or feeder protection where nuisance tripping on leakage from distributed loads must be avoided; Type A detects pulsating DC residual currents common in electronics and single-phase rectifier loads. Voltage-independent tripping means the RCD operates even if the phase voltage collapses — critical for safety when the supply is degraded.

Terminal tunnel accepts 1…35 mm² rigid or 1…25 mm² flexible cable; tighten to 3.5 N·m. IP20 finger-safe on the body, IP40 inside a modular enclosure. Ambient range -25…60 °C operating, -40…85 °C storage.

Frequently asked questions

How do I get current pricing and availability for A9W24363?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time against independent distribution channels — no stock count or price is published here.

What is the closest alternative to A9W24363 in this component family?

Within the Acti9 Vigi iC60 family, the primary variant difference is rated current and sensitivity. This 63 A / 300 mA Type A version is the highest-current instantaneous Type A in the add-on RCD line; a 40 A or 30 mA variant would be a different order code. No pin-compatible drop-in exists with a different rating.

What compliance documentation does this brand provide for A9W24363?

The A9W24363 is certified to EN 61009-1 and IEC 61009-1 for RCDs, and IEC 60947-2 for insulation coordination (pollution degree 3, 6 kV impulse withstand). Schneider Electric provides a Declaration of Performance (DoP) and CE/UKCA marking; RoHS and REACH compliance is standard for the Acti9 range.

MPN
A9W24363