It is rated 25 A with a 30 mA sensitivity, Type A (pulsating DC and sinusoidal AC fault detection), and operates at 230 V AC 50/60 Hz in a 1P+N pole configuration. For a panel OEM or MRO planner: this is the add-on module, not a standalone RCBO — it needs a mechanical and electrical link to an Acti9 MCB (screw connection). The 30 mA trip threshold suits standard socket-outlet and lighting circuit protection in residential or commercial distribution boards. Type A covers electronic loads like washing machines, LED drivers, and IT equipment that generate pulsed DC fault currents — a common requirement in modern installations.
Depth is 74 mm, height 102.5 mm — standard for the Acti9 modular range. Terminal tunnel accepts 1–16 mm² rigid or 1–10 mm² flexible; strip length 14 mm, tighten to 2 N·m. IP20 finger-safe front; the modular enclosure is rated IP40 inside the panel.