It is rated 25 A with 30 mA sensitivity, Type A-SI (Super Immunised), meaning it handles sinusoidal AC and pulsed DC fault currents while resisting nuisance tripping from high-frequency harmonics or transient surges common on modern electronic loads.
Mounts via clip-on to DIN rail (35 mm) and connects to the load side of a 1P+N MCB using the supplied screw terminals. The 36 mm width occupies two 9 mm pitches, leaving space for adjacent modules in a consumer unit or distribution board. Pollution degree 3 per EN/IEC 61009-2-1 suits standard industrial and commercial panel environments where some conductive pollution is expected.
Earth-leakage protection class
Type A-SI (Super Immunised) means this RCD is voltage-independent — it trips on residual current without needing an external supply — and is immune to unwanted tripping from 50 Hz harmonics, switching transients, and up to 3 kHz waveforms. This makes it a direct fit for circuits feeding variable-speed drives, LED drivers, UPS equipment, or other loads that generate high-frequency leakage. The instantaneous time delay means no intentional delay before tripping on a fault.