Rated 25 A at 400 V AC, 50/60 Hz, with a 300 mA sensitivity and Type A-SI (Super Immunised) waveform discrimination, it is built to sit downstream of a main breaker in a DIN-rail enclosure and provide instantaneous earth-leakage tripping. The 3-pole (3P) configuration matches a three-phase outgoing circuit.
Clip-on mounting to DIN rail, 4 x 9 mm pitch modules wide (90 mm). The tunnel-type terminals accept 1…16 mm² rigid or 1…10 mm² flexible cable; strip 14 mm and torque to 2 N·m. The device sits as an outgoer in the panel, electrically connected to the upstream MCB by screws. IP20 on the body, IP40 inside the modular enclosure — standard for a distribution board, not for wet-area standalone mounting.
Type A-SI (Super Immunised) means the device is resistant to nuisance tripping from high-frequency earth-leakage currents generated by VFDs, UPS systems, or switched-mode power supplies — a common requirement on mixed-load outgoing circuits.