EV-charger RCCB — Type B-EV, 25 A, 30 mA
What sets this unit apart is its Type B-EV protection class — it detects AC, pulsating DC, smooth DC, and high-frequency residual currents up to 100 kHz, which is exactly what an electric vehicle charger injects back onto the line. The 30 mA trip threshold means it meets the personal-protection requirement for socket-outlet circuits per IEC 60364-7-722, so an EVSE installation downstream of this RCCB is code-compliant for shock protection.
Clip-on mounting to a standard DIN rail, 2-pole (2P) wide at 72 mm — that is 8 module pitches of 9 mm each. Neutral is on the left. The 79 mm depth clears most enclosure gland plates without interference.
Certified to IEC 61008-2-1, IEC/EN 62423, and EN 61008-2-1. Carries VDE, NF, IMQ, and KEMA quality marks. Pollution degree 3, overvoltage category IV, rated insulation voltage 250 V. The 8/20 µs impulse withstand is 3 kA per EN/IEC 61008-1.