Schneider Electric Altivar Process Modular APM1A0C16N4RH power module, 160 kW normal duty / 132 kW heavy duty at 380-480 V, 302 A continuous output, IP00, cabinet mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

APM1A0C16N4RH — Identification
ParameterValue
Product typePower module
Device short nameAPM
Product range / familyAltivar Process Modular
APM1A0C16N4RH — Power & Output
ParameterValue
Motor power (kW)160 kW at 380...480 V (normal duty) 132 kW at 380...480 V (heavy duty)
Continuous output current302 A at 2.5 kHz for normal duty 250 A at 2.5 kHz for heavy duty
Apparent power223 kVA at 380...480 V normal duty 181 kVA at 380...480 V heavy duty
APM1A0C16N4RH — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 10...10 %
Network number of phases3 phases
APM1A0C16N4RH — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
APM1A0C16N4RH — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP degree of protectionIP00 conforming to IEC 61800-5-1 IP21 (for cabinet integration) conforming to IEC 61800-5-1 IP54 (for cabinet integration) conforming to IEC 61800-5-1
APM1A0C16N4RH — Environmental
ParameterValue
Operating ambient temperature-10...40 °C (without derating) 40...50 °C (with derating factor)
Operating altitude<= 4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
APM1A0C16N4RH — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Product details

160 kW power module for the Altivar Process Modular platform

The APM1A0C16N4RH is a power module in the Schneider Electric Altivar Process Modular range, designed for cabinet integration with synchronous or asynchronous motors up to 160 kW at 380-480 V in normal duty, or 132 kW in heavy duty. Continuous output current is 302 A at 2.5 kHz for normal duty and 250 A at 2.5 kHz for heavy duty, with a permissible temporary boost of 1.1 x In for 60 s (normal duty) or 1.5 x In for 60 s (heavy duty) — the overload ceiling that governs motor acceleration and process upset recovery.

The 302 A continuous output at 2.5 kHz switching frequency sets the thermal limit for the IGBT stage; raising the switching frequency to 8 kHz requires derating per the adjustable 2-8 kHz range, which reduces the usable current below the 302 A ceiling. Apparent power is 223 kVA at 380-480 V normal duty, 181 kVA heavy duty — the kVA figure drives transformer and cable sizing upstream, not the motor nameplate. The integrated EMC filter meets IEC 61800-3 category C3 with 300 m of motor cable — this means the drive is intended for industrial power networks (not residential) and suppresses conducted emissions enough to avoid nuisance tripping of upstream RCDs within that cable length. IP00 on the module itself, but the cabinet integration path supports IP21 or IP54 per IEC 61800-5-1, and UL Type 1 or Type 12 per UL 61800-5-1 — the enclosure rating is determined by the cabinet build, not the module alone.

Active production, sourced per BOM quantity

The kit includes the power module, mains unit, 48 V power supply for the fan, relay for the fan, three fuse holders, and mounting brackets with hardware — no separate ordering of sub-assemblies for the basic build.

Cabinet integration checklist — dimensions, altitude, environment

Cabinet-mount only, vertical orientation within ±10 degrees. Dimensions are 1230 mm height, 230 mm width, 510 mm depth — the height is the dominant panel-space constraint; plan for top-entry cable glands and adequate clearance above for the fan exhaust. Operating altitude up to 4800 m with current derating above 1000 m — at 2000 m expect roughly 10-15 % derating on the continuous output current; above that the derating steepens per IEC 61800-5-1. Ambient temperature range is -10 to 40 °C without derating, 40 to 50 °C with derating factor. Pollution degree 2 per IEC 61800-5-1 — the cabinet must maintain a clean, non-conductive environment. Chemical pollution resistance class 3C3 and dust pollution resistance class 3S3 per IEC 60721-3-3 — suitable for cement plants, chemical processing, and other harsh industrial environments where airborne contaminants are present.

CE marked and complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic emissions), IEC 60721-3 (environmental classification), IEC 61508 (functional safety), and IEC 13849-1 (safety-related parts of control systems). EMC immunity includes electrostatic discharge test level 3, radiated RF field test level 3, fast transient/burst test level 4, surge test level 3, and conducted RF immunity test level 3 per the respective IEC 61000-4-x standards — the module is hardened for industrial electrical noise environments. Shock resistance is 7 gn for 11 ms per IEC 60068-2-27; vibration resistance is 1.5 mm peak-to-peak at 2-13 Hz and 0.5 gn at 13-200 Hz per IEC 60068-2-6 — figures that matter for transport and installation in high-vibration applications like conveyors or crushers.

Frequently asked questions

What motors does APM1A0C16N4RH support?

It is designed for both synchronous and asynchronous motors, covering the majority of industrial AC motor types used in pump, fan, conveyor, and compressor applications.

What is the overload capability of APM1A0C16N4RH?

Normal duty allows 1.1 x In for 60 seconds; heavy duty allows 1.5 x In for 60 seconds. This overload ceiling determines whether the drive can handle motor acceleration and process transients without tripping.

What compliance documentation does Schneider Electric provide for APM1A0C16N4RH?

The module is CE marked and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. UL Type 1 and Type 12 enclosure ratings are supported per UL 61800-5-1 for cabinet integration.