The APM1L0CCM115: The module carries an IP00 rating as a bare component, but when integrated into a cabinet it can achieve IP21 or IP66 depending on the enclosure design — so the final protection class is a cabinet-build decision, not a module-level spec. The EMC filter is omitted by default (no C3 category filter), meaning the cabinet builder must supply external filtering if the installation requires conducted emission limits below IEC 61800-3 C3. Operating ambient is -10 to 40 °C without derating, and 40 to 50 °C with derating applied. Altitude derating kicks in above 1000 m, up to 4800 m. The switching frequency is adjustable from 2 to 4.9 kHz, with a derating factor that scales with frequency — useful for matching motor acoustic noise targets without oversizing the module.
CE marked and carries UL 61800-5-1, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Pollution degree 2 per IEC 61800-5-1. Chemical and dust resistance rated 3C3 / 3S3 per IEC 60721-3-3. EMC immunity tested to level 3 or 4 across the standard transient, surge, and RF fields.