Skip to main content
Schneider Electric APM6A0CTLN401 — AC Drive (VFD) 480V

Schneider APM6A0CTLN401 Altivar Process control module, 380-

MPNAPM6A0CTLN401
Active

Schneider Electric Altivar Process Modular, APM6A0CTLN401 control module, 380...480 V supply, STO SIL3, Modbus TCP/Ethernet, IP00.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

APM6A0CTLN401 — Identification
ParameterValue
Product typeControl module
Device short nameAPM
Product range / familyAltivar Process Modular

Input / Supply

APM6A0CTLN401 — Input / Supply
ParameterValue
Rated supply voltage range380...480 V
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm 500 V DC for 1 minute to earth

Mechanical & Cooling

APM6A0CTLN401 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529
Acoustic noise level69 dB conforming to 86/188/EEC

Environmental

APM6A0CTLN401 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C (without derating) 40...50 °C (with derating factor)
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

APM6A0CTLN401 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Protection & EMC

APM6A0CTLN401 — Protection & EMC
ParameterValue
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

Communication

APM6A0CTLN401 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The Schneider APM6A0CTLN401 is the control module for the Altivar Process Modular drive range, rated 380...480 V supply and carrying STO (Safe Torque Off) SIL 3 as a standard safety function.

Supply rails and wiring

The module needs three separate supply rails: 24 V DC (19...30 V) for digital inputs, a regulated 10.5 V DC ±5 % for an external 1 to 10 kΩ reference potentiometer, and 24 V DC (21...27 V) for the digital inputs and STO logic. The insulation test is 1 MΩ at 500 V DC for one minute to earth.

Safety and compliance

The module carries CE marking and is designed to IEC 61800-3 (EMC environment), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental classification), and IEC 61508 / IEC 13849-1 for functional safety.

Thermal and environmental limits

Operates from -10 to 40 °C without derating, and up to 50 °C with derating. Power dissipation hits 2390 W at a 2.5 kHz switching frequency under forced convection. Pollution degree 2 per IEC 61800-5-1, and chemical/dust resistance class 3C3 / 3S3 per IEC 60721-3-3.

Communications and fieldbus

Ethernet/Modbus TCP at 10/100 Mbit/s via RJ45 on the remote graphic terminal, plus Modbus serial at 4.8 to 38.4 kbit/s (2-wire RS-485, RTU frame) on a second RJ45. Supports half/full duplex and autonegotiation. Modbus serial addressing from 1 to 247, with configurable parity (8-bit, odd/even/none).

Frequently asked questions

What supply voltages does the APM6A0CTLN401 need?

Three rails: 24 V DC (19...30 V) for digital inputs, 10.5 V DC ±5 % for a reference potentiometer (1 to 10 kΩ), and 24 V DC (21...27 V) for digital inputs and STO.

What communication protocols does the APM6A0CTLN401 support?

Ethernet/Modbus TCP at 10/100 Mbit/s and Modbus serial (RS-485) at 4.8 to 38.4 kbit/s.

MPN
APM6A0CTLN401