Skip to main content
Schneider Electric APM6A0CTLY6 — AC Drive (VFD) 600V

Schneider APM6A0CTLY6 Altivar Process Control Module, STO SI

MPNAPM6A0CTLY6
Active

Schneider Electric Altivar Process Modular APM6A0CTLY6 control module, 500...690 V, STO SIL 3, Modbus TCP/Ethernet, IP00.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

APM6A0CTLY6 — Identification
ParameterValue
Product range / seriesAltivar Process Modular
Device short name / model codeAPM
Product / component typeControl module
APM6A0CTLY6 — Electrical (input)
ParameterValue
Rated supply voltage500...690 V
Supply frequency50...60 Hz - 5...5 %
Max. input current THD (THDi)<48 % full load conforming to IEC 61000-3-12
APM6A0CTLY6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 for Modbus serial
Data format8 bits, configurable odd, even or no parity for Modbus serial
APM6A0CTLY6 — Environmental
ParameterValue
IP rating (with kit options)IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529
Operating ambient temperature-10...40 °C (without derating) 40...50 °C (with derating factor)
Storage temperature-40...70 °C
Operating altitude (with derating)1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Pollution degree2 conforming to IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance7 gn for 11 ms conforming to IEC 60068-2-27
Acoustic noise level69 dB conforming to 86/188/EEC
APM6A0CTLY6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

The Schneider APM6A0CTLY6 is the control module for the Altivar Process Modular drive range, rated 500...690 V supply. It packs STO (Safe Torque Off) rated SIL 3, so it handles the safety separation without a separate safety relay in many configurations. Communication runs over Ethernet/Modbus TCP and Modbus serial, with a remote graphic terminal via RJ45.

Supply and signal conditioning

Digital inputs take 24 V DC (19...30 V), and there's a separate internal 24 V (21...27 V) rail for the STO circuit. The module also provides a 10.5 V DC ±5 % reference for a 1 to 10 kΩ potentiometer — handy if you're wiring a speed pot directly to the control unit without an external supply.

Safety and environment

STO is SIL 3 per IEC 61508, so it's suitable for safety functions up to that integrity level. Pollution degree 2, vibration resistance to 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz, and shock rated at 7 gn for 11 ms. Ambient operating range is -10 to 40 °C without derating, 40 to 50 °C with derating. Storage from -40 to 70 °C.

Communications and fieldbus

Ethernet/Modbus TCP runs at 10/100 Mbit/s, half/full duplex with auto-negotiation. Modbus serial uses 2-wire RS-485 at 4.8 to 38.4 kbit/s, RTU frame, slave addresses 1–247. Data format is 8 bits with configurable parity. The remote graphic terminal connects via RJ45 for both Ethernet and serial.

Frequently asked questions

What are the key supply voltages for this control module?

The module requires 24 V DC (19...30 V) for digital inputs, a separate 24 V DC (21...27 V) for STO, and provides a 10.5 V DC ±5 % reference for a 1 to 10 kΩ potentiometer.

What communication protocols are available?

Ethernet/Modbus TCP at 10/100 Mbit/s and Modbus serial via 2-wire RS-485 at up to 38.4 kbit/s.

What is the operating temperature range?

-10 to 40 °C without derating, 40 to 50 °C with derating. Storage range is -40 to 70 °C.

MPN