MPNAPMCA03LCN4RH
Active
electronic filtering power supply, 400V, 268A, IP00, 3 phases
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Power filter |
| Device short name | APM |
| Product range / family | Altivar Process Modular |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 380...480 V - 10...10 % |
| Input line current | 278 A at 380 V (normal duty) 268 A at 480 V (normal duty) 233 A at 380 V (heavy duty) 218 A at 480 V (heavy duty) |
| Network number of phases | 3 phases |
Power & Output
| Parameter | Value |
|---|---|
| Apparent power | 223 kVA normal duty 181 kVA heavy duty |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated with 300 m category C3 |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Prospective short-circuit current (Isc) | 50 kA |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529 |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -10...40 °C (without derating) 40...50 °C (with derating factor) |
| Operating altitude | <= 4800 m with current derating above 1000m |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 |
| Storage / transport temperature | -40...70 °C |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | UL 61800-5-1 IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 |
MPN
APMCA03LCN4RH