ATH230D15N4
Schneider Electric ATH230D15N4
MPNATH230D15N4
Active
Variable speed drive, Altivar HVAC ATH200, ATH230, 15kW, 20hp, 380 to 500V, 3 phase, IP20, with EMC filter
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Device short name | ATH230 |
| Product range / family | Altivar HVAC ATH200 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 15 kW |
| Max. transient current | 36.4 A |
| Apparent power | 28.8 kVA at 500 V |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 380...500 V - 15...10 % |
| Input line current | 47.3 A 380 V 33.3 A 500 V |
Control & Performance
| Parameter | Value |
|---|---|
| Asynchronous motor control modes | Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points |
| Synchronous motor control modes | Vector control without sensor |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated |
| Protection functions | Line supply phase loss drive Motor phase loss motor Line supply overvoltage and undervoltage drive Overheating protection drive Overload motor With PTC probes motor Short-circuit between motor phases drive Overcurrent between output phases and earth drive |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Prospective short-circuit current (Isc) | 22 kA |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 |
| Acoustic noise level | 58 dB |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | 14...122 °F (-10...50 °C) without derating 122...140 °F (50...60 °C) with derating factor |
| Operating altitude | 3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m |
| Relative humidity | 5...95 % without condensation or dripping water EN/IEC 60068-2-3 |
| Storage / transport temperature | -13...158 °F (-25...70 °C) |
| Pollution degree | 2 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CULus CE UKCA KC EAC ATEX RCM |
| Standards compliance | IEC 61800-5-1 IEC 61800-3 UL 508C IEC 61800-3 environment 1 category C2 IEC 61800-3 environments 2 category C3 IEC 60721-3 IEC 61508 IEC 13849-1 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | Modbus serial BACnet MS/TP |
MPN
ATH230D15N4