Specifications
| Parameter | Value |
|---|---|
| Product range / series | Altivar HVAC ATH200 |
| Device short name / model code | ATH230 |
| Product / component type | Variable speed drive |
| Parameter | Value |
|---|---|
| Rated supply voltage | 525...600 V - 15...10 % |
| Supply frequency | 50...60 Hz - 5...5 % |
| Line (input) current | 22.1 A 525 V 20.1 A 600 V |
| Prospective line short-circuit current (Isc) | 22 kA |
| EMC filter | Without EMC filter |
| Parameter | Value |
|---|---|
| Apparent power | 20.9 kVA at 600 V |
| Switching (PWM) frequency | 2...16 kHz adjustable 4...16 kHz with derating |
| Parameter | Value |
|---|---|
| Communication protocols | Modbus serial BACnet MS/TP |
| Address range | 0...247 0...127 |
| Data format | 8 bits, configurable odd, even or no parity 1or 2 stop |
| Parameter | Value |
|---|---|
| Mounting mode | Cabinet mount |
| Product destination / compatibility | Asynchronous motors Synchronous motors |
| Parameter | Value |
|---|---|
| IP rating (with kit options) | IP20 |
| Operating ambient temperature | 14...122 °F (-10...50 °C) without derating 122...140 °F (50...60 °C) with derating factor |
| Storage temperature | -13...158 °F (-25...70 °C) |
| Operating altitude (with derating) | 3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m |
| Relative humidity | 5...95 % without condensation or dripping water EN/IEC 60068-2-3 |
| Pollution degree | 2 |
| Acoustic noise level | 58 dB |
| Parameter | Value |
|---|---|
| Standards | IEC 61800-5-1 IEC 61800-3 UL 508C IEC 61800-3 environment 1 category C2 IEC 61800-3 environments 2 category C3 IEC 60721-3 IEC 61508 IEC 13849-1 |
| Agency markings / approvals | CULus CE UKCA KC EAC ATEX RCM |