Skip to main content
Schneider Electric ATH230D22N4 — AC Drive (VFD) 480V

Schneider Electric ATH230D22N4 Altivar HVAC Drive, 22 kW

MPNATH230D22N4
Active

Schneider Electric Altivar HVAC ATH200 series, ATH230D22N4, AC Drive (VFD) 480V, 22 kW, 3-phase, cabinet mount, standard version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH230D22N4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH230
Product range / familyAltivar HVAC ATH200
ATH230D22N4 — Power & Output
ParameterValue
Motor power (kW)22 kW
Max. transient current50.6 A
Apparent power42.8 kVA at 500 V
ATH230D22N4 — Input / Supply
ParameterValue
Rated supply voltage range380...500 V - 15...10 %
Input line current64.6 A 380 V 49.4 A 500 V
ATH230D22N4 — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH230D22N4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsLine supply phase loss drive Motor phase loss motor Line supply overvoltage and undervoltage drive Overheating protection drive Overload motor With PTC probes motor Short-circuit between motor phases drive Overcurrent between output phases and earth drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Prospective short-circuit current (Isc)22 kA
ATH230D22N4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20
Acoustic noise level64 dB
ATH230D22N4 — Environmental
ParameterValue
Operating ambient temperature14...122 °F (-10...50 °C) without derating 122...140 °F (50...60 °C) with derating factor
Operating altitude3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m
Relative humidity5...95 % without condensation or dripping water EN/IEC 60068-2-3
Storage / transport temperature-13...158 °F (-25...70 °C)
Pollution degree2
ATH230D22N4 — Approvals
ParameterValue
Certifications & markingCULus CE UKCA KC EAC ATEX RCM
Standards complianceIEC 61800-5-1 IEC 61800-3 UL 508C IEC 61800-3 environment 1 category C2 IEC 61800-3 environments 2 category C3 IEC 60721-3 IEC 61508 IEC 13849-1
ATH230D22N4 — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

22 kW HVAC drive with STO and BACnet/IP

The ATH230D22N4 is a 22 kW Altivar HVAC ATH200 drive for 3-phase 480 V fan and pump loads. Rated line current is 64.6 A at 380 V and 49.4 A at 500 V, with 42.8 kVA apparent power at 500 V. This is the standard version — no coating or extended I/O — meant for clean indoor cabinet mounting. It carries integrated STO (Safe Torque Off) at SIL 3 / PL e, so it can serve in safety-rated applications without an external safety relay for the stop function. The integrated EMC filter meets IEC 61800-3 environment 1 category C2 and environment 2 category C3, covering both residential and industrial second-environment installations.

Built for fan and pump duty

The drive includes fire mode, run-permissive, PID controller, damper control, and underload detection for broken belt — all standard. The BACnet/IP communication module is an option card slot; the base unit has a 2-wire RS-485 physical interface supporting Modbus serial and BACnet MS/TP at 38.4 or 76.8 kbit/s. Cabinet mount, vertical +/- 10 degrees. Operating altitude is 1000 to 3000 m with 1% current derating per 100 m above 1000 m. Pollution degree 2, relative humidity 5-95% non-condensing. Noise level is 64 dB — expect audible fan noise in a quiet machine room.

Frequently asked questions

Where can I buy ATH230D22N4 and how do I get a price?

Available through independent distribution. No stock-holding claim — quoted per order.

What compliance documentation does Schneider Electric provide for ATH230D22N4?

The drive carries CULus, CE, UKCA, KC, EAC, ATEX, and RCM markings. Standards compliance includes IEC 61800-5-1, IEC 61800-3, UL 508C, IEC 61508, and ISO 13849-1. ATEX certification supports use with motors in potentially explosive atmospheres.

What is ATH230D22N4's listed depth?

Depth is 9.02 inches (229 mm). Width is 7.09 inches (180 mm), height is 15.4 inches (390 mm). Cabinet mount, vertical orientation.

What phase is ATH230D22N4?

Three-phase input and output. Output voltage is less than or equal to the supply voltage. Supply frequency is 50/60 Hz.

MPN
ATH230D22N4