Skip to main content
Schneider Electric ATH630C13N4Z — AC Drive (VFD) 480V

Schneider Electric ATH630C13N4Z Altivar ATH600 VFD, 200 hp

MPNATH630C13N4Z
Active

Schneider Electric Altivar ATH600 ATH630C13N4Z AC drive, 200 hp normal duty / 150 hp heavy duty, 132 kW / 110 kW, 237 A at 380 V normal duty, cabinet mount, STO SIL 3, IP20, 82 kg.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH630C13N4Z — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH630
Product range / familyAltivar HVAC ATH600
ATH630C13N4Z — Power & Output
ParameterValue
Motor power (kW)132 kW for normal duty 110 kW for heavy duty
Max. transient current275.0 A during 60 s (normal duty) 316.5 A during 60 s (heavy duty)
Apparent power177.1 kVA (normal duty) 137.2 kVA (heavy duty)
ATH630C13N4Z — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current237 A at 380 V (normal duty) 213 A at 480 V (normal duty) 201 A at 380 V (heavy duty) 165 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH630C13N4Z — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH630C13N4Z — Protection & EMC
ParameterValue
Integrated EMC filter classClass C3 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
ATH630C13N4Z — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00
Acoustic noise level69.9 dB
ATH630C13N4Z — Environmental
ParameterValue
Operating ambient temperature-15...50 °C without derating 50...60 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH630C13N4Z — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH630C13N4Z — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

Motor power and duty ratings

The ATH630C13N4Z: Rated 200 hp normal duty and 150 hp heavy duty (132 kW / 110 kW), with line current 237 A at 380 V normal duty and 213 A at 480 V normal duty; heavy duty pulls 201 A at 380 V and 165 A at 480 V.

Safety and compliance

Integrated STO (safe torque off) function, certified SIL 3 per IEC 61508 and PL e per ISO 13849-1. That means the drive can be used in a safety circuit up to Cat 4 / PL e without an external safety relay — the STO input is dual-channel and monitored. Marked CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, KCC. Complies with UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, RoHS.

Application-specific functions

Includes fire mode, forced fire mode, run permissive, PID controller with 3 additional PID loops, damper control, underload detection for broken belt, scroll compressor management, skipped frequencies, catch on the fly, power monitoring, and cybersecure firmware update. The fire mode overrides all protection to keep the fan running in smoke-extraction duty — the drive will run until it fails, which is the intended behaviour for life-safety systems.

No pin-compatible alternative in the Altivar ATH600 family — the ATH630C13N4Z is the standard version for this power class.

Frequently asked questions

What is the closest pin-compatible alternative to ATH630C13N4Z in this AC drive family?

No pin-compatible alternative is listed within the Altivar ATH600 series. The ATH630C13N4Z is the standard version for the 200 hp / 132 kW normal-duty class.

What compliance documentation does Schneider Electric provide for ATH630C13N4Z?

The drive carries CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, KCC markings and complies with UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and RoHS.

MPN