Skip to main content
Schneider Electric ATH630D22N4Z — AC Drive (VFD) 480V

Schneider Electric ATH630D22N4Z Altivar HVAC Drive

MPNATH630D22N4Z
Active

Schneider Electric Altivar HVAC ATH600 series, ATH630D22N4Z AC drive, 22 kW/30 hp normal duty, 18.5 kW/25 hp heavy duty, 480 V, cabinet mount, 13.7 kg.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH630D22N4Z — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH630
Product range / familyAltivar HVAC ATH600
ATH630D22N4Z — Power & Output
ParameterValue
Motor power (kW)22 kW for normal duty 18.5 kW for heavy duty
Max. transient current50.9 A during 60 s (normal duty) 58.8 A during 60 s (heavy duty)
Apparent power28.6 kVA (normal duty) 24.9 kVA (heavy duty)
ATH630D22N4Z — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current39.6 A at 380 V (normal duty) 34 A at 480 V (normal duty) 34.1 A at 380 V (heavy duty) 29.9 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH630D22N4Z — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH630D22N4Z — Protection & EMC
ParameterValue
Integrated EMC filter classClass C2 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
ATH630D22N4Z — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20
Acoustic noise level59.5 dB
ATH630D22N4Z — Environmental
ParameterValue
Operating ambient temperature-15...50 °C without derating 50...60 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH630D22N4Z — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH630D22N4Z — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

Dual-duty power ratings and line current

The ATH630D22N4Z is a 22 kW (30 hp) normal-duty drive with a heavy-duty rating of 18.5 kW (25 hp). The normal-duty line current is 39.6 A at 380 V and 34 A at 480 V; heavy-duty line current drops to 34.1 A at 380 V and 29.9 A at 480 V.

Safety and compliance stack

Safe Torque Off (STO) is built in, certified to SIL 3 per IEC 61508 and PL e per ISO 13849-1. That eliminates the need for an external safety relay on the motor power circuit for most guarding applications. The integrated Class C2 EMC filter covers conducted emissions for first-environment (residential) installations, so you do not need an add-on filter for most European and UKCA markets.

Application-specific firmware features

This drive ships with HVAC-specific functions: fire mode, forced fire mode, damper control, broken-belt detection via underload, scroll compressor management, and skipped frequencies to avoid mechanical resonances. The PID controller supports three additional PID sets, useful for multi-zone pressure or temperature control. Catch on the fly lets it re-synchronise to a spinning motor without a coast-to-stop cycle.

Frequently asked questions

What safety functions does the ATH630D22N4Z include?

Safe Torque Off (STO) is integrated and certified to SIL 3 (IEC 61508) and PL e (ISO 13849-1). This covers the motor power removal function for most guarding circuits without an external safety relay.

What compliance markings does the ATH630D22N4Z carry?

CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, and KCC. The drive also meets UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1.

How can I order the ATH630D22N4Z or check availability?

This drive is sourced to order against the BOM quantity. Submit an RFQ for current pricing and lead time; availability is confirmed at quote time through independent distribution channels.

MPN
ATH630D22N4Z