Skip to main content
Schneider Electric ATH630D90N4Z — AC Drive (VFD) 480V

Schneider ATH630D90N4Z Altivar 630 VFD, 90 kW ND, 480V

MPNATH630D90N4Z
Active

Schneider Electric Altivar HVAC ATH600 series, ATH630D90N4Z AC drive (VFD), 90 kW / 125 hp normal duty, 75 kW / 100 hp heavy duty, 480 V, cabinet mount, 54.6 kg.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH630D90N4Z — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH630
Product range / familyAltivar HVAC ATH600
ATH630D90N4Z — Power & Output
ParameterValue
Motor power (kW)90 kW for normal duty 75 kW for heavy duty
Max. transient current190.3 A during 60 s (normal duty) 217.5 A during 60 s (heavy duty)
Apparent power112.9 kVA (normal duty) 98.2 kVA (heavy duty)
ATH630D90N4Z — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current156.2 A at 380 V (normal duty) 136 A at 480 V (normal duty) 134 A at 380 V (heavy duty) 118 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH630D90N4Z — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH630D90N4Z — Protection & EMC
ParameterValue
Integrated EMC filter classClass C3 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
ATH630D90N4Z — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00
Acoustic noise level62.4 dB
ATH630D90N4Z — Environmental
ParameterValue
Operating ambient temperature-15...50 °C without derating 50...60 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH630D90N4Z — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH630D90N4Z — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

What the ATH630D90N4Z drives and where it fits

The ATH630D90N4Z is a 90 kW normal-duty (75 kW heavy-duty) AC drive from the Altivar HVAC ATH600 series, purpose-built for pump, fan, and compressor loads in commercial HVAC and light industrial applications. It delivers 112.9 kVA apparent power in normal duty and 98.2 kVA in heavy duty, with a line current of 156.2 A at 380 V (normal) or 118 A at 480 V (heavy).

Safety and compliance — STO, SIL 3, and global marks

Safe Torque Off (STO) is integrated as standard, certified to SIL 3 per IEC 61508 and PL = e per ISO 13849-1. This eliminates the need for an external safety relay in many guarding circuits — the drive itself removes torque from the motor when the STO input is de-energised. The drive carries CE, UKCA, CULus, EAC, RCM, ATEX, and KCC markings, and complies with UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. RoHS and WEEE compliance is confirmed — no exemptions to chase for EU-market shipments.

Application-specific functions built in

Beyond basic V/Hz and sensorless vector control, the drive includes fire mode, forced fire mode, run permissive, PID controller with three additional PID sets, damper control, underload detection for broken belt, scroll compressor management, skipped frequencies, catch on the fly, and cybersecure firmware update. These are not optional cards — they are standard in the firmware, configurable via the integrated keypad or fieldbus. The control supply is 24 V DC (19...30 V) from an external source; the digital inputs and STO are powered internally at 24 V DC. Communication options include Modbus RTU, BACnet MS/TP, and optional PROFINET, Ethernet IP/Modbus TCP, or BACnet IP via communication modules.

Frequently asked questions

What compliance documentation does Schneider Electric provide for ATH630D90N4Z?

The drive is marked CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, RoHS, and KCC. It complies with UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. RoHS and WEEE compliance is confirmed.

MPN