Skip to main content
Schneider Electric ATH630U22N4Z — AC Drive (VFD) 480V

Schneider Electric ATH630U22N4Z Altivar HVAC Drive, 2.2 kW

MPNATH630U22N4Z
Active

Schneider Electric Altivar HVAC ATH600, ATH630U22N4Z, 2.2 kW / 3 hp normal duty VFD, 1.5 kW / 2 hp heavy duty, 380-480 V three-phase, integrated C2 EMC filter, STO SIL 3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH630U22N4Z — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH630
Product range / familyAltivar HVAC ATH600
ATH630U22N4Z — Power & Output
ParameterValue
Motor power (kW)2.2 kW for normal duty 1.5 kW for heavy duty
Max. transient current5.6 A during 60 s (normal duty) 5.6 A during 60 s (heavy duty)
Apparent power3.2 kVA (normal duty) 2.3 kVA (heavy duty)
ATH630U22N4Z — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current4.837 A at 380 V (normal duty) 3.8 A at 480 V (normal duty) 3.5 A at 380 V (heavy duty) 2.8 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH630U22N4Z — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH630U22N4Z — Protection & EMC
ParameterValue
Integrated EMC filter classClass C2 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)5 kA
ATH630U22N4Z — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20
Acoustic noise level47 dB
ATH630U22N4Z — Environmental
ParameterValue
Operating ambient temperature-15...50 °C without derating 50...60 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH630U22N4Z — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH630U22N4Z — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

The ATH630U22N4Z is a 2.2 kW normal-duty / 1.5 kW heavy-duty VFD from the Altivar HVAC ATH600 series, sized for a 3 hp motor on 380-480 V three-phase supply. Line current pulls 4.837 A at 380 V normal duty, 3.8 A at 480 V normal duty; heavy-duty figures are 3.5 A and 2.8 A respectively. The integrated Class C2 EMC filter covers most commercial installations without an external box. The control circuit needs an external 24 V DC supply (19...30 V); the drive generates its own 24 V for digital inputs and STO internally.

Three relay outputs are built in: R1 offers one NO and one NC contact; R2 and R3 each provide one NO contact, all rated for 100,000 cycles. Analog inputs AI1-AI3 carry ±1.5 % accuracy over a 60 °C swing; analog outputs AQ1-AQ2 hold ±1 %.

Frequently asked questions

What compliance documentation does this drive carry?

The drive is marked CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, RoHS, and KCC. It complies with UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1.

What are the key ratings for this drive?

Normal duty: 2.2 kW / 3 hp, line current 4.837 A at 380 V or 3.8 A at 480 V. Heavy duty: 1.5 kW / 2 hp, line current 3.5 A at 380 V or 2.8 A at 480 V. Apparent power is 3.2 kVA normal duty, 2.3 kVA heavy duty.

What communication options fit this drive?

The drive accepts option cards for BACnet IP, PROFINET, and Ethernet IP/Modbus TCP. The built-in serial port supports Modbus RTU and BACnet MS/TP over a 2-wire RS-485 physical layer at baud rates from 4800 to 76.8 kbit/s.

MPN
ATH630U22N4Z