Duty ratings and motor power
The ATH650D37N4 is rated for 37 kW (50 hp) in normal duty and 30 kW (40 hp) in heavy duty, with the line current at 480 V normal duty being 57 A and 48.3 A in heavy duty. The heavy-duty rating at 380 V draws 54.8 A, which is the higher current condition to check when sizing upstream protection.
Safety function and SIL 3
The drive integrates Safe Torque Off (STO) certified to SIL 3 per IEC 61508 and PL e per ISO 13849-1, which means it can be used as the primary safety isolation in a drive safety circuit without an external contactor. STO removes the motor torque without disconnecting the mains power, so the drive control power and fieldbus communication remain active during the safety demand.
Integrated EMC filter and compliance
The Class C2 EMC filter is integrated, covering conducted emissions for most industrial environments up to the first environment (domestic/commercial) with restricted distribution. Markings include CE, UKCA, CULus, EAC, RCM, ATEX, and KCC, covering European, North American, Eurasian, Australian, and Korean regulatory jurisdictions.
Application-specific functions
Built-in fire mode, forced fire mode, scroll compressor management, damper control, and underload detection for broken belt are standard firmware features, so no additional option card is needed for these HVAC and pumping applications. The drive supports catch on the fly and power monitoring, which reduces nuisance trips when the motor is already spinning.