Specifications

ATH650U15N4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH650
Product range / familyAltivar HVAC ATH600
ATH650U15N4 — Power & Output
ParameterValue
Motor power (kW)1.5 kW for normal duty 0.75 kW for heavy duty
Max. transient current4.1 A during 60 s (normal duty) 3.3 A during 60 s (heavy duty)
Apparent power2.2 kVA (normal duty) 1.4 kVA (heavy duty)
ATH650U15N4 — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current3.463 A at 380 V (normal duty) 2.7 A at 480 V (normal duty) 2 A at 380 V (heavy duty) 1.7 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH650U15N4 — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH650U15N4 — Protection & EMC
ParameterValue
Integrated EMC filter classClass C2 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)5 kA
ATH650U15N4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP55 Type 12
Acoustic noise level47 dB
ATH650U15N4 — Environmental
ParameterValue
Operating ambient temperature-15...40 °C without derating 40...50 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH650U15N4 — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH650U15N4 — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

The Schneider ATH650U15N4 is an Altivar HVAC ATH600 series drive sized for a 1.5 kW motor at normal duty or 0.75 kW at heavy duty on 380-480 V three-phase supply. Line current draws 3.463 A at 380 V normal duty, 2.7 A at 480 V normal duty; heavy duty pulls 2 A at 380 V and 1.7 A at 480 V. Integrated Class C2 EMC filter is onboard, so no external filter needed for most commercial installations. Safety function is STO rated SIL 3 / PL e.

Integration notes

Wall-mount only, vertical position. Dimensions are 247 mm deep, 189 mm wide, 375 mm tall. Control circuit requires an external 24 V DC supply (19...30 V).

Functions and protection

Built-in functions include fire mode, forced fire mode, PID controller with 3 additional PID, damper control, underload detection for broken belt, scroll compressor management, skipped frequencies, catch on the fly, power monitoring, and cybersecure firmware update. Protection covers motor thermal overload, STO, motor phase loss, overspeed, drive overheating, output short-circuit, DC bus overvoltage, line supply over/undervoltage, and control circuit break.

Frequently asked questions

What are the key ratings for the ATH650U15N4?

Motor power is 1.5 kW normal duty, 0.75 kW heavy duty. Line current at 380 V normal duty is 3.463 A; at 480 V normal duty it is 2.7 A. Output frequency is 0.4 kHz. Safety function is STO at SIL 3 / PL e.

What compliance markings does the ATH650U15N4 carry?

Markings include CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, KCC. Standards met include UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and RoHS.

What communication protocols does the ATH650U15N4 support?

Native protocols are Modbus RTU and BACnet MS/TP over 2-wire RS-485. Optional communication modules add PROFINET, Ethernet IP/Modbus TCP, or BACnet IP.

MPN