Skip to main content
Schneider Electric ATH650U40N4 — AC Drive (VFD) 480V

Schneider Altivar ATH650U40N4 HVAC Drive, 4 kW Normal Duty

MPNATH650U40N4
Active

Schneider Electric Altivar HVAC ATH600 series, ATH650U40N4, 4.0 kW normal duty / 3.0 kW heavy duty, 380-480 V, STO SIL 3, integrated C2 EMC filter, wall mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATH650U40N4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATH650
Product range / familyAltivar HVAC ATH600
ATH650U40N4 — Power & Output
ParameterValue
Motor power (kW)4.0 kW for normal duty 3.0 kW for heavy duty
Max. transient current10.0 A during 60 s (normal duty) 10.8 A during 60 s (heavy duty)
Apparent power5.0 kVA (normal duty) 3.9 kVA (heavy duty)
ATH650U40N4 — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current6.956 A at 380 V (normal duty) 6 A at 480 V (normal duty) 5.4 A at 380 V (heavy duty) 4.7 A at 480 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control circuit: 24 V DC (19...30 V), Internal supply for digital inputs and STO: 24 V DC (20.4...27 V), Internal supply for reference potentiometer: 10.5 V DC +/- 5 %, <10 mA, protection type: short-circuit
ATH650U40N4 — Control & Performance
ParameterValue
Asynchronous motor control modesVoltage/frequency ratio, 5 points Flux vector control with sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points
Synchronous motor control modesVector control without sensor
ATH650U40N4 — Protection & EMC
ParameterValue
Integrated EMC filter classClass C2 EMC filter integrated
Protection functionsThermal overload protection: motor Safe torque off: motor Motor phase loss: motor Against exceeding limit speed: motor Temperature protection: drive Overheating: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)5 kA
ATH650U40N4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP55 Type 12
Acoustic noise level53 dB
ATH650U40N4 — Environmental
ParameterValue
Operating ambient temperature-15...40 °C without derating 40...50 °C with derating factor
Operating altitude1000 m without derating 1000...3000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2
ATH650U40N4 — Approvals
ParameterValue
Certifications & markingCE UKCA CULus EAC RCM ATEX WEEE ROHS KCC
Standards complianceUL 61800-5-1 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 RoHS
ATH650U40N4 — Communication
ParameterValue
Communication protocolsModbus serial BACnet MS/TP

Product details

The Schneider Altivar ATH650U40N4 is a standard-variant HVAC drive from the ATH600 series, sized for a 4.0 kW motor at normal duty or 3.0 kW at heavy duty on 380–480 V three-phase supply. Normal-duty line current draws 6.956 A at 380 V and 6 A at 480 V; heavy-duty drops to 5.4 A and 4.7 A respectively. Apparent power runs 5.0 kVA normal, 3.9 kVA heavy. The integrated Class C2 EMC filter covers most European installations without an external add-on. Safety function is STO (safe torque off) rated SIL 3 per IEC 61508 and PL e per ISO 13849-1 — enough for most machine-safety architectures without a separate safety relay. The drive also packs thermal overload, motor phase loss, overcurrent, overvoltage, and undervoltage protections as standard. Fire mode and forced fire mode are available for smoke-extraction or pressurization sequences.

Markings include CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, and KCC. Standards referenced are UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and RoHS. The ATEX marking means the drive can be part of an ATEX-rated installation when paired with appropriate motor and cabling — not that the drive itself is Ex-certified as a standalone device. Documentation packs (declaration of conformity, CE/UKCA DoC, RoHS reports) are available on request.

Frequently asked questions

What safety functions does the ATH650U40N4 support?

STO (safe torque off) rated SIL 3 per IEC 61508 and PL e per ISO 13849-1. The drive also includes thermal overload, motor phase loss, overcurrent, overvoltage, and undervoltage protection.

What are the physical dimensions of the ATH650U40N4?

Height 375 mm, width 189 mm, depth 254 mm. Weight is 5.1 kg. Wall-mount only, vertical position.

What certifications and compliance documents are available for the ATH650U40N4?

Markings include CE, UKCA, CULus, EAC, RCM, ATEX, WEEE, ROHS, and KCC. Standards: UL 61800-5-1, EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, RoHS. Declarations of conformity and RoHS reports are available on request.

MPN
ATH650U40N4