Skip to main content
Schneider Electric ATV1200A135001010 — AC Drive (VFD) 480V

Schneider Electric ATV1200A135001010 AC Drive, 11286 kW

MPNATV1200A135001010
Active

Schneider Electric Altivar 1200 ATV1200A135001010 AC drive, 11286 kW motor power, 13500 kVA apparent power, 48-pulse diode rectifier, 2970…3630 V supply, floor-standing enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV1200A135001010 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200
ATV1200A135001010 — Power & Output
ParameterValue
Motor power (kW)11286 kW
Continuous output current624 A (high overload) 779 A (standard overload)
Max. transient current935 A for 60 s
Apparent power13500 kVA
ATV1200A135001010 — Input / Supply
ParameterValue
Rated supply voltage range10 kV +/- 10 %
Input line current850 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)
ATV1200A135001010 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVector control with sensor, optional Closed-loop control with encoder Voltage/frequency ratio (V/f) Sensorless flux vector control
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder
ATV1200A135001010 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms
ATV1200A135001010 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP41 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows
ATV1200A135001010 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)
ATV1200A135001010 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1
ATV1200A135001010 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

11286 kW motor power, 13500 kVA apparent power

The Schneider Electric ATV1200A135001010 is an Altivar 1200 AC drive rated for 11286 kW motor power and 13500 kVA apparent power, supplied from a 2970…3630 V line via a 48-pulse diode rectifier bridge. That 48-pulse topology keeps input harmonics low enough to avoid a separate filter on most utility feeds — the integrated EMC filter handles the rest. Overload capability is specified at 1.2 In for 60 s and 1.5 In for 3 s under standard overload, with a high-overload profile reaching 1.5 In for 60 s and 1.85 In for 3 s. This means the drive can ride through short-duration load spikes without tripping, which matters for crushers, mills, or conveyors that see intermittent peak torque.

Floor-standing enclosure with separate air flows

The drive ships in a floor-standing enclosure with separate air flows for the power section and control compartment — the forced-convection cooling moves 160000 m³/h (standard efficiency). The physical footprint is substantial: 3040 mm high, 15680 mm wide, 1700 mm deep. Plan for a dedicated equipment room or outdoor shelter with adequate ventilation; the noise level at full fan speed is 80 dB. The enclosure colour is grey (RAL 7032). Electrical connection uses M10 screw-type bars with a clamping capacity of 6 x 40 mm² for the line input (/R, /S, L3/T), entry from the top or bottom.

Active production, quoted to order

The drive is CE marked and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Electrical isolation between power and control circuits is standard, with a dielectric strength of 28 kV AC between earth and power terminals.

Frequently asked questions

What is the ATV1200A135001010 used for?

It is a medium-voltage AC drive designed for asynchronous motors up to 11286 kW. Typical applications include large pumps, fans, compressors, conveyors, and mill drives in heavy industry where the 48-pulse input keeps harmonic distortion low enough to meet IEEE 519 without external filtering.

MPN
ATV1200A135001010