Schneider Electric ATV1200A15854242 — AC Drive (VFD) 480V

Schneider ATV1200A15854242 AC Drive, 1325 kW, 1585 kVA

MPNATV1200A15854242
Obsolete

Schneider Electric Altivar 1200 ATV1200A15854242 medium-voltage AC drive, 1325 kW motor power, 1585 kVA, 24-pulse diode rectifier, 2970-3630 V input, floor-standing enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV1200A15854242 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200
ATV1200A15854242 — Power & Output
ParameterValue
Motor power (kW)1325 kW
Continuous output current220 A (standard overload) 176 A (high overload)
Max. transient current264 A for 60 s
Apparent power1585 kVA
ATV1200A15854242 — Input / Supply
ParameterValue
Rated supply voltage range4.16 kV +/- 10 %
Input line current220 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)
ATV1200A15854242 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVector control with sensor, optional Voltage/frequency ratio (V/f) Closed-loop control with encoder Sensorless flux vector control
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder
ATV1200A15854242 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms
ATV1200A15854242 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP41 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows
ATV1200A15854242 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)
ATV1200A15854242 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1
ATV1200A15854242 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

1325 kW medium-voltage drive with 24-pulse rectifier

The ATV1200A15854242 is a medium-voltage AC drive rated for 1325 kW motor power and 1585 kVA apparent power, supplied from a 2970-3630 V three-phase line through a 24-pulse diode rectifier bridge. The 24-pulse topology cancels the 5th, 7th, 11th, and 13th harmonics at the input, keeping total harmonic distortion low enough that an external harmonic filter is often unnecessary — a real advantage for brownfield sites with weak utility ties or genset supply. The drive sits in a floor-standing enclosure with separate air flows for the power cells and the phase-shifting transformer, so hot air from the transformer doesn't recirculate through the IGBT cells. The standard-efficiency variant draws 16500 m³/h of cooling air; the high-efficiency variant pulls 19900 m³/h — the difference matters when sizing the room ventilation louver or the roof fan.

Physical footprint and site access

At 2670 mm high, 4060 mm wide (standard efficiency) or 4360 mm wide (high efficiency), and 1600 mm deep (high efficiency) or 1500 mm deep (standard efficiency), this is not a drive you slide into an existing panel — it needs a dedicated electrical room with a concrete pad and overhead lifting provisions. The M10 bar terminals on the line side accept up to 6 x 40 mm² conductors per phase, entry from bottom or top, so the cable trench or overhead tray must align with the gland plate. The enclosure is grey RAL 7032, and the operating position is vertical ±10 degrees — no tilting it into a tight corner. Vibration resistance is 4.9 m/s² from 10 to 50 Hz, which covers normal floor vibration in an industrial substation but not a reciprocating compressor skid.

Overload profiles and motor compatibility

The drive supports two overload profiles. Standard overload: 1.2 x In for 60 seconds or 1.5 x In for 3 seconds. High overload: 1.5 x In for 60 seconds or 1.85 x In for 3 seconds. The high overload profile suits applications with heavy breakaway torque — crushers, mills, or extruders — where the motor needs 150 % current for a full minute to get the load turning. Standard overload is enough for centrifugal pumps and fans. The drive is designed for both synchronous and asynchronous motors, with a speed range of 20 to 100 %. Output voltage is limited to the supply voltage — there is no step-up transformer inside the drive, so the motor must be wound for the incoming line voltage. The 20 kV AC dielectric strength between earth and power terminals gives solid isolation for medium-voltage service.

The ATV1200A15854242 carries CE marking and complies with EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (immunity), and EN/IEC 61800-5-1 (safety). Overvoltage category II applies, so the drive expects the installation to have surge suppression upstream at the MV transformer secondary. The integrated EMC filter covers conducted emissions for the first environment (industrial) per EN/IEC 61800-3. No external filter is needed for a standard industrial installation, but a site with a residential supply boundary may require an additional external filter on the input.

The product composition includes two plinths, a phase-shifting transformer, medium-voltage arrestors, cooling fans, a human-machine interface, and 12 power cells. The 12-cell architecture is the core of the 24-pulse design — each cell is a single-phase IGBT inverter fed from a separate secondary winding on the transformer. If a cell faults, the drive can often continue running at reduced capacity until a replacement cell arrives.

Frequently asked questions

What input voltage does the ATV1200A15854242 require?

The supply voltage limits are 2970 to 3630 V AC, with a 24-pulse diode rectifier input. The line current at rated load is 220 A, and the prospective short-circuit current withstand is 31.5 kA for 150 ms.

MPN