Skip to main content
Schneider Electric ATV1200A18303333 — AC Drive (VFD) 480V

Schneider ATV1200A18303333 AC Drive, 1530 kW, 1830 kVA, 3 kV

MPNATV1200A18303333
Active

Schneider Electric Altivar 1200 ATV1200A18303333 medium-voltage AC drive, 1530 kW motor power, 1830 kVA apparent power, 2970...3630 V supply, 18-pulse diode rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A18303333 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A18303333 — Power & Output
ParameterValue
Motor power (kW)1530 kW
Continuous output current320 A (standard overload) 256 A (high overload)
Max. transient current384 A for 60 s
Apparent power1830 kVA

Input / Supply

ATV1200A18303333 — Input / Supply
ParameterValue
Rated supply voltage range3.3 kV +/- 10 %
Input line current320 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A18303333 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesClosed-loop control with encoder Vector control with sensor, optional Sensorless flux vector control Voltage/frequency ratio (V/f)
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder

Protection & EMC

ATV1200A18303333 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A18303333 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP41 IP31 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A18303333 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A18303333 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A18303333 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

Active production — 1530 kW medium-voltage drive for synchronous and asynchronous motors

The ATV1200A18303333: Supply voltage range is 2970...3630 V AC, fed through an 18-pulse diode rectifier bridge that reduces line harmonics below IEEE 519 thresholds without an external filter. The drive handles synchronous and asynchronous motors with standard overload: 1.2 In for 60 s or 1.5 In for 3 s. High-overload duty delivers 1.5 In for 60 s and 1.85 In for 3 s.

Floor-standing enclosure — physical footprint and cooling air volume

Assembled in a floor-standing enclosure with separate air flows for power and control sections. Standard-efficiency configuration measures 1500 mm deep × 4560 mm wide × 2670 mm high; high-efficiency adds depth to 1700 mm and width to 4860 mm. Forced-convection cooling moves 19,800 m³/h (standard) or 23,100 m³/h (high efficiency) through the cabinet. Noise level at full fan speed is 80 dB. Operating altitude from 1000 m to 2000 m requires current derating of 0.6 % per 100 m above 1000 m. Pollution degree 2 per EN/IEC 61800-5-1 applies.

Internal architecture — phase-shifting transformer and power cells

The drive comprises a phase-shifting transformer, 9 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. The 18-pulse input stage cancels the 5th and 7th harmonics at the transformer secondary. Electrical isolation between power and control circuits is maintained throughout. Dielectric strength tested at 10 kV AC between earth and power terminals. Prospective line short-circuit current withstand is 31.5 kA for 150 ms. Ground fault protection is integrated on the drive side.

Control I/O and compliance documentation

Four software-configurable analogue inputs accept 0...20 mA or 4...20 mA, 24 V max, 250 Ω impedance. Two analogue outputs offer the same current ranges. Six discrete inputs are standard, expandable to 10. External control supply is 220 V AC at 3 kVA; internal cooling fan supply is 380 V AC. Optional external supplies for both control and fan are available. CE marked. Conforms to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1. Integrated EMC filter simplifies panel compliance.

Frequently asked questions

What is the motor power rating for ATV1200A18303333?

The drive is rated for 1530 kW motor power at 1830 kVA apparent power, with a supply voltage range of 2970...3630 V AC.

What compliance documentation does Schneider Electric provide for ATV1200A18303333?

CE marking is standard. The drive conforms to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1. Integrated EMC filter is included.

MPN
ATV1200A18303333